5-6
5.1.6
Wiring of main circuit terminals and grounding terminals
Perform wiring in the order given below. This section also outlines terminal functions.
Primary grounding terminal ( G) for inverter enclosure
Two grounding terminals ( G) are not exclusive to the power supply wiring (primary circuit) or motor
wiring (secondary circuit).
Be sure to ground either of the two grounding terminals for safety and noise reduction. The inverter is
designed for use with safety grounding to avoid electric shock, fire and other disasters.
1) Ground the inverter in compliance with the national or local electric code.
2) Use a thick grounding wire with a large surface area and keep the wiring length as short as possible.
Inverter output terminals U, V, and W and secondary grounding terminals ( G) for motor
Inverter's output terminals should be connected as follows:
1) Connect the three wires of the 3-phase motor to terminals U, V, and W, aligning the phases each
other.
2) Connect the grounding wire of output lines (U, V, and W) to the grounding terminal ( G).
When there is more than one combination of an inverter and motor, do not use a multicore
cable for the purpose of handling their wirings together.
Use shielded wires for the motor cable and route the cable as short as possible. Clamp the
shield to the specified point inside the inverter.
DC reactor terminals P1 and P(+)
(on inverters of 110 kW or above)
Connect terminals [P1] and [P(+)] of a DC reactor (DCR) bundled as standard for power factor
correction to these terminals.
• The wiring length should be 10 m or below.
• When an AC power supply is connected, be sure to connect a DCR.
• If a PWM converter is connected to the inverter, no DCR is required.
DC link bus terminals P(+) and N(-)
For connection to the DC link bus.
When you need to use the DC link bus terminals P(+) and N(-), consult your Fuji Electric
representative.
Main circuit power input terminals L1/R, L2/S, and L3/T (three-phase input)
The three-phase input power lines are connected to these terminals.
1) For safety, make sure that the molded case circuit breaker (MCCB) or magnetic contactor (MC) is
turned OFF before wiring the main circuit power input terminals.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...