6.3 Details of Function Codes
6-285
Chap. 6
FUNCTION C
ODES
Selecting Feedback Terminals
For feedback control, determine the connection terminal according to the type of the sensor
output.
• If the sensor is a current output type, use the current input terminal [C1] of the inverter.
• If the sensor is a voltage output type, use the voltage input terminal [12] of the inverter, or
switch over the terminal [V2] to the voltage input terminal and use it.
For details, refer to the descriptions of E61 through E63.
Application example: Process control (for air conditioners, fans and pumps)
The operating range for PID process control is internally controlled as 0% through 100%. For
the given feedback input, determine the operating range to be controlled by means of gain
adjustment.
(Example) When the output level of the external sensor is within the range of 1 to 5 V:
• Use terminal [12] designed for voltage input.
• Set the gain (C32 for analog input adjustment) at 200% in order to make the maximum
value (5 V) of the external sensor's output correspond to 100%. Note that the input
specification for terminal [12] is 0 to 10 V corresponding to 0 to 100%; thus, a gain factor
of 200% (= 10 V
÷
5 V
×
100) should be specified. Note also that any bias setting does not
apply to feedback control.
(Example 1) When the output level of the external sensor is
±
7 VDC:
• Use terminal [12] since the voltage input is of bipolar.
• When the external sensor's output is of bipolar, the inverter controls the speed within the
range of
±
100%. To convert the output
±
7 VDC to
±
100%, set the gain (C32 for analog
input adjustment) at 143% as calculated below.
10 V
7 V
≈
143%
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...