6.3 Details of Function Codes
6-55
Chap. 6
FUNCTION C
ODES
F07, F08
Acceleration Time 1, Deceleration Time 1
E10, E12, E14 (Acceleration Time 2, 3 and 4)
E11, E13, E15 (Deceleration Time 2, 3 and 4)
H07 (Acceleration/Deceleration Pattern)
H56 (Deceleration Time for Forced Stop)
F07 specifies the acceleration time, the length of time the frequency increases from 0 Hz to
the maximum frequency. F08 specifies the deceleration time, the length of time the frequency
decreases from the maximum frequency down to 0 Hz.
- Data setting range: 0.00 to 3600.00 (s)
Acceleration/deceleration time
Function code
Acceleration/
deceleration time
ACC
time
DEC
time
Switching factor of acceleration/deceleration time
(
Refer to the descriptions of E01 to E07.)
RT2
RT1
Acceleration/
deceleration time 1
F07 F08
OFF OFF
Acceleration/
deceleration time 2
E10 E11 OFF ON
Acceleration/
deceleration time 3
E12 E13 ON OFF
Acceleration/
deceleration time 4
E14 E15 ON
ON
The combinations of ON/OFF states of
the two terminal commands
RT2
and
RT1
offer four choices of acceleration/
deceleration time 1 to 4. (Data = 4, 5)
If no terminal command is assigned,
only the acceleration/deceleration time 1
(F07/F08) is effective.
Force to stop
-
H56
If terminal command
STOP
(data = 30) is turned OFF, the
inverter decelerates to a stop with the deceleration time
specified by H56. After that, the inverter displays alarm Er6
and enters an alarm state.
Acceleration/Deceleration pattern (H07)
H07 specifies the acceleration and deceleration patterns (patterns to control output
frequency).
Data
for
H07
Acceleration/
deceleration
pattern
Motion
Function
code
0 Linear
The inverter runs the motor with the constant acceleration and
deceleration.
-
1
S-curve
(Weak)
Weak:
The acceleration/deceleration rate to
be applied to all of the four
inflection zones is fixed at 5% of the
maximum frequency.
-
2
S-curve
(Strong)
To reduce an impact that
acceleration/deceleration
would make on the machine,
the inverter gradually
accelerates or decelerates the
motor in both the starting
and ending zones of
acceleration or deceleration.
Strong:
The acceleration/deceleration rate to
be applied to all of the four
inflection zones is fixed at 10% of
the maximum frequency.
-
3
Curvilinear
Acceleration/deceleration is linear below the base frequency
(constant torque) but it slows down above the base frequency to
maintain a certain level of load factor (constant output).
This acceleration/deceleration pattern allows the motor to accelerate
or decelerate with the maximum performance of the motor.
-
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...