4.3 Peripheral Equipment
4-5
Chap. 4
SEL
ECT
ING PE
RIPH
ER
AL
EQUI
PME
N
T
4.3 Peripheral
Equipment
4.3.1
Molded case circuit breaker (MCCB),
residual-current-operated protective device (RCD)/earth
leakage circuit breaker (ELCB) and magnetic contactor (MC)
[ 1 ] Functional overview
MCCBs and RCDs/ELCBs*
* With overcurrent protection
Molded Case Circuit Breakers (MCCBs) are designed to protect the power circuits between the power
supply and inverter's main circuit terminals ([L1/R], [L2/S] and [L3/T]) from overload or short-circuit,
which in turn prevents secondary accidents caused by the broken inverter.
Residual-Current-Operated Protective Devices (RCDs)/Earth Leakage Circuit Breakers (ELCBs)
function in the same way as MCCBs.
Built-in overcurrent/overload protective functions protect the inverter itself from failures related to its
input/output lines.
MCs
An MC can be used at both the power input and output sides of the inverter. At each side, the MC
works as described below. When inserted in the output circuit of the inverter, the MC can also switch
the motor drive power supply between the inverter output and commercial power lines.
At the power supply side
Insert an MC in the power supply side of the inverter in order to:
(1) Forcibly cut off the inverter from the power supply (generally, commercial/factory power lines)
with the protective function built into the inverter, or with the external signal input.
(2) Stop the inverter operation in an emergency when the inverter cannot interpret the stop command
due to internal/external circuit failures.
(3) Cut off the inverter from the power supply when the MCCB inserted in the power supply side
cannot cut it off for maintenance or inspection purpose. For the purpose only, it is recommended
that you use an MC capable of turning the MC ON/OFF manually.
Avoid frequent ON/OFF operation of the magnetic contactor (MC) in the input circuit;
otherwise, the inverter failure may result.
The frequency of the MC's ON/OFF should not be more than once per 30 minutes. To assure
10-year or longer service life of the inverter, it should not be more than once per hour.
If frequent start/stop of the motor is required, use
FWD
/
REV
terminal signals or the ,
and keys on the inverter's keypad.
At the output side
Insert an MC in the power output side of the inverter in order to:
(1) Prevent externally turned-around current from being applied to the inverter power output
terminals ([U], [V], and [W]) unexpectedly. An MC should be used, for example, when a circuit
that switches the motor driving power supply between the inverter output and commercial power
lines is connected to the inverter.
If a magnetic contactor (MC) is inserted in the inverter's output (secondary) circuit for
switching the motor to a commercial power or for any other purposes, it should be switched
on and off when both the inverter and motor are completely stopped. This prevents the
contact point from getting rough due to a switching arc of the MC. The MC should not be
equipped with any main circuit surge killer (Fuji SZ-ZM
, etc.).
Applying a commercial power to the inverter's output circuit breaks the inverter. To avoid it,
interlock the MC on the motor's commercial power line with the one in the inverter output
circuit so that they are not switched ON at the same time.
(2) Drive more than one motor selectively by a single inverter.
(3) Selectively cut off the motor whose thermal overload relay or equivalent devices have been
activated.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...