6-182
Overload prevention control --
OLP
(E20 to E24 and E27, data = 36)
This output signal comes ON when the overload prevention control is activated and the
output frequency changed.
In equipment where a decrease in the output frequency does not lead to a decrease in
the load, the overload prevention control is of no use and should not be enabled.
H71
Deceleration Characteristics
Setting the H71 data to "1" enables forced brake control. If regenerative energy produced
during the deceleration of the motor and returned to the inverter exceeds the inverter’s
braking capability, an overvoltage trip will occur. The forced brake control increases the
motor energy loss during deceleration, increasing the deceleration torque.
Data for H71
Function
0 Disable
1 Enable
This function is aimed at controlling the torque during deceleration; it has no effect
if there is a braking load.
Enabling the automatic deceleration (anti-regenerative control, H69 = 2 or 4) in the
torque limit control mode disables the deceleration characteristics specified by H71.
H72
Main Power Down Detection (Mode selection)
H72 monitors the inverter alternate-current input power source, and disables the inverter
operation if it is not established.
Data for H72
Function
0 Disable
1 Enable
In cases where the power is supplied via a PWM converter or the inverter is connected via the
DC link bus, there is no alternate-current input. In such cases, set H72 data to "0," otherwise
the inverter cannot operate.
If you use a single-phase power supply, contact your Fuji Electric representative.
H76
Torque Limiter for Braking (Frequency increment limit)
(Refer to H69.)
For details, refer to the description of H69.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...