6.3 Details of Function Codes
6-149
Chap. 6
FUNCTION C
ODES
Object function codes
Initialize to:
E21: Terminal [Y2] Function
167: Motor 4 being driven by commercial
power (
M4_L
)
E22: Terminal [Y3] Function
165: Motor 3 being driven by commercial
power (
M3_L
)
E23: Terminal [Y4] Function
163: Motor 2 being driven by commercial
power (
M2_L
)
E24: Terminal [Y5] Function
161: Motor 1 being driven by commercial
power (
M1_L
)
E62: Terminal [C1] Extended Function
5: PID feedback value 1
E63: Terminal [V2] Extended Function
32: Auxiliary input 2 to PID process command
C64: Analog Input Adjustment for
Terminal [C1] (Display unit)
44: bar
C65: Analog Input Adjustment for
Terminal [C1] (Maximum scale)
10.00
H91: Current Input Wire Break Detection
0.5 s
J101: PID Control 1 (Mode selection)
1: Enable (Process control, normal operation)
J110: PID Control 1 P (Gain)
2.500 times
J111: PID Control 1 I (Integral time)
0.2 s
J149: Slow Flowrate Stop Function (Mode
selection)
1: Manual operation (stop judgment: MV)
J150: Slow Flowrate Stop Function
(Operation level)
35.00 Hz
J151: Slow Flowrate Stop Function
(Elapsed time)
15 s
J157: Slow Flowrate Stop Function
(Cancel frequency)
38.0 Hz
J158: Slow Flowrate Stop Function
(Cancel deviation level 1)
5.00
J159: Slow Flowrate Stop Function
(Cancel delay timer)
1 s
J401: Pump Control Mode Selection
1: Enable (Inverter drive motor fixed system)
J411: Motor 1 Mode Selection
1: Enable
J412: Motor 2 Mode Selection
1: Enable
J413: Motor 3 Mode Selection
1: Enable
J414: Motor 4 Mode Selection
1: Enable
J415: Motor 5 Mode Selection
1: Enable
J425: Motor Switching Procedure
1: Equal operating time (Cumulative run time of
each motor is equalized.)
J450: Motor Increase Judgment (Judgment
frequency)
48 Hz
J451: Motor Increase Judgment (Duration
time)
5.00 s
J452: Motor Decrease Judgment
(Judgment frequency)
30 Hz
J453: Motor Decrease Judgment (Duration
time)
1.00 s
J456: Motor Increase Switching Level
50%
J457: Motor Increase PID Control Start
Frequency
35 Hz
J459: Motor Decrease Switching Level
50%
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...