Connecting programmable logic controller (PLC) to terminal [Y1], [Y2], [Y3]
or [Y4]
Figure 2.9 shows two examples of circuit connection between the transistor output of
the inverter’s control circuit and a PLC. In example (a), the input circuit of the PLC
serves as a SINK for the control circuit output, whereas in example (b), it serves as a
SOURCE for the output.
C0
+24 VD
C
Programmable
logic controller
SINK input
Photocoupler
<Control circuit>
[Y1]
to
[Y4]
[CMY]
31 to
35 V
Current
C0
Programmable
logic controller
SOURCE input
+24 VD
C
Photocoupler
<Control circuit>
[Y1]
to
[Y4]
[CMY]
31 to
35 V
Current
T
ransist
or output
(a) PLC serving as SINK
(b) PLC serving as SOURCE
Figure 2.9 Connecting PLC to Control Circuit
[Y5A/C]
General-purpose
relay output
(1) A general-purpose relay contact output usable as well as the
function of the transistor output terminal [Y1], [Y2], [Y3] or
[Y4].
Contact rating: 250 VAC 0.3 A, cos
φ
= 0.3, 48 VDC, 0.5 A
(2) Switching of the normal/negative logic output is applicable to
the following two contact output modes: "Active ON"
(Terminals [Y5A] and [Y5C] are closed (excited) if the signal
is active.) and "Active OFF" (Terminals [Y5A] and [Y5C] are
opened (non-excited) if the signal is active while they are
normally closed.).
Relay
ou
tpu
t
[30A/B/C]
Alarm relay
output
(for any error)
(1) Outputs a contact signal (1C) when the protective function has
been activated to stop the motor.
Contact rating: 250 VAC, 0.3A, cos
φ
= 0.3, 48 VDC, 0.5A
(2) Any one of output signals assigned to terminals [Y1] to [Y4]
can also be assigned to this relay contact to use it for signal
output.
(3) Switching of the normal/negative logic output is applicable to
the following two contact output modes: "Active ON"
(Terminals [30A] and [30C] are closed (excited) if the signal is
active.) and "Active OFF" (Terminals [30A] and [30C] are
opened (non-excited) if the signal is active while they are
normally closed.).
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...