9.4 Nothing appears on the monitor
9-23
Chap. 9
TROUBL
ESH
OOTING
9.4 Nothing appears on the monitor
9.4.1
Abnormal motor operation
[ 1 ] The motor does not rotate.
Possible Causes
What to Check and Suggested Measures
(1) No power supplied to the
inverter.
Check the input voltage and interphase voltage unbalance.
Î
Turn ON a molded case circuit breaker (MCCB), a residual-current-
operated protective device (RCD)/earth leakage circuit breaker
(ELCB) (with overcurrent protection) or a magnetic contactor (MC).
Î
Check for voltage drop, phase loss, poor connections, or poor
contacts, and fix them if necessary.
Î
If only the auxiliary control power input is supplied, also supply the
main power to the inverter.
(2) No forward/reverse operation
command was inputted, or
both the commands were
inputted simultaneously
(external signal operation).
Check the input status of the forward/reverse command with Menu "I/O
Checking" using the keypad.
Î
Input a run command.
Î
Set either the forward or reverse operation command to off if both
commands are being inputted.
Î
Correct the run command source. (Set F02 data to "1.")
Î
Correct the assignment of commands
FWD
and
REV
with function
codes E98 and E99.
Î
Connect the external circuit wires to control circuit terminals [FWD]
and [REV] correctly.
Î
Make sure that the sink/source slide switch (SW1) on the control
printed circuit board (control PCB) is properly configured.
(3) No indication of rotation
direction (keypad operation).
Check the input status of the forward/reverse rotation direction command
with Menu "I/O Checking" using the keypad.
Î
Input the rotation direction (F02 = 0), or select the keypad operation
with which the rotation direction is fixed (F02 = 2 or 3).
(4) The inverter could not accept
any run commands from the
keypad since it was in
Programming mode.
Check which operation mode the inverter is in, using the keypad.
Î
Shift the operation mode to Running mode and enter a run command.
(5) A run command with higher
priority than the one attempted
was active, and the run
command was stopped.
Referring to the block diagram of the frequency command block (refer to
Chapter 7), check the higher priority run command with Menu "Data
Checking" and Menu "I/O Checking" using the keypad.
Î
Correct any incorrect function code data settings (in H30, y98, etc.)
or cancel the higher priority run command.
(6) No analog frequency
command input.
Check whether the analog frequency command (reference frequency) is
correctly inputted, using Menu #4 "I/O Checking" on the keypad.
Î
Connect the external circuit wires to terminals [13], [12], [11], [C1],
and [V2] correctly.
Î
When the terminal [C1] is used, check the slider position of the
terminal [C1] property switch (SW5) and the setting of the thermistor
mode selection (H26).
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...