6.3 Details of Function Codes
6-189
Chap. 6
FUNCTION C
ODES
6.3.6
H1 codes (High performance functions)
H104 Number-of-resets Clear Time
H04, H05 (Auto-reset (Times and Reset interval))
H104 specifies the time for clearing the number of resets counted.
The inverter clears the number of retries counted if
After restart following a reset, if the inverter output frequency comes to be constant and an
alarm that causes a reset does not occur during the number-of-resets clear time (H104), then
the inverter clears the number of resets counted.
- Data setting range: 0.5 to 5.0 (min)
< Operation timing scheme >
• In the figure below, normal operation restarts in the 3rd retry. (An alarm that causes a reset
does not occur during the time specified by H104.)
H105
H106
Retry Target Selection
H04, H05 (Auto-reset (Times and Reset interval))
H104 (Number-of-retry Clear Time)
To set and display the retry alarm factors in binary format, each retry alarm factor has been
assigned to bits 0 to 7 as listed in Table 6.1 and Table 6.2.
Retry target selection 1 (H105)
Table 6.1 H105 Retry Target Selection 1, Bit Assignment of Selectable Factors
Indication on
the LCD
0 0 0 0 0 0 0 0
Bit 7 6 5 4 3 2 1 0
Protective
function
- -
Motor
overheat
Motor
overload
-
Overheat
protection
Overvoltage
protection
Overcurrent
protection
Alarm code
-
-
OH4
OL1
-
OH1
OH3
OLU
OV1
OV2
OV3
OC1
OC2
OC3
- Data setting range: 00000000 to 11111111 (binary)
Number of resets
Clear the number of
resets counted.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...