Control of Maximum Starts per Hour (motor)
(Input selection)
(Number of slow flowrate stop detections)
This detects frequent occurrence of start and slow flowrate stop due to the failure of
accumulators or other equipment. As for the inverter, it is possible to select whether operation
is to be stopped with alarm or operation is to be continued with warming being output.
If the number of initiations exceeds the number of slow flowrate stop detections (J169) within
the number-of-detection clearing time (J170), the control of maximum starts per hour (motor)
becomes active in a short period of time.
Control of maximum starts per hour (motor) (Input selection) (J168)
J168 specifies the protection mode for control of the maximum starts per hour.
- Data setting range: 0 to 2
Data for J168
Operation description
0 Disable
1
Alarm (inverter stop with roC trip)
* After alarm is canceled, Control of maximum starts per hour (motor) is
started when the first slow flowrate stop occurs.
2 Warning
output
* After warning is canceled, Control of maximum starts per hour (motor) is
started when the first slow flowrate stop occurs.
Operations regarding control of maximum starts per hour can be monitored from
external equipment, by assigning
L-ALM
("Light alarm") to any of [Y1] to [Y4],
[Y5A/C] and [30A/B/C]. (E20 to E24 and E27, data = 98)
Control of maximum starts per hour (motor) (Number of slow flowrate stop detections)
(J169)
Set the number of stops as a detection condition.
- Data setting range: 1 to 10
The number of slow flowrate stop detections (J169) is cleared when one of the following
conditions is satisfied.
• When a set period of time has elapsed
• When the run command is OFF (stop)
• When PID control cancel is performed
• When alarm is generated
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...