6.2 Function Code Tables
6-35
Chap. 6
FUNCTION C
ODES
y codes: Link Functions
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
y01 RS-485
Communication
1
(Station
address)
0 to 255
* Set 1 when other than BACnet is 0.
* Set 127 when BACnet is 128 or above.
N Y 1
y02
(Communications error processing) 0: Immediately trip with alarm Er8
1: Trip with alarm Er8 after running for the period specified by
timer y03
2: Retry during the period specified by timer y03. If the retry fails,
trip with alarm Er8.
If it succeeds, continue to run.
3: Continue to run
Y Y 0
y03
(Timer) 0.0 to 60.0 s
Y Y 2.0
y04
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Y Y 3
y05
(Data length) 0: 8 bits
1: 7 bits
Y Y 0
y06
(Parity check) 0: None (2 stop bits)
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
Y Y 0
y07
(Stop bits) 0: 2 bits
1: 1 bit
Y Y 0
y08
(No-response error detection time) OFF: No detection, 1 to 60 s
Y Y
OFF
y09
(Response interval) 0.00 to 1.00 s
Y Y
0.01
y10
(Protocol
selection) 0:
Modbus
RTU
protocol
1: SX protocol (loader protocol)
2: Fuji general-purpose inverter protocol
3: Metasys N2 protocol
5: BACnet protocol
Y Y 1
y11 RS-485
Communication
2
(Station
address)
0 to 255
N Y 1
y12
(Communications error processing) 0: Immediately trip with alarm ErP
1: Trip with alarm ErP after running for the period specified by
timer y13
2: Retry during the period specified by timer y13. If the retry fails,
trip with alarm ErP. If it succeeds, continue to run.
3: Continue to run
Y Y 0
y13
(Timer) 0.0 to 60.0 s
Y Y 2.0
y14
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Y Y 3
y15
(Data length) 0: 8 bits
1: 7 bits
Y Y 0
y16
(Parity check) 0: None (2 stop bits)
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
Y Y 0
y17
(Stop bits) 0: 2 bits
1: 1 bit
Y Y 0
y18
(No-response error detection time) OFF: No detection, 1 to 60 s
Y Y
OFF
y19
(Response interval) 0.00 to 1.00 s
Y Y
0.01
y20
(Protocol
selection) 0:
Modbus
RTU
protocol
1: SX protocol (loader protocol)
2: Fuji general-purpose inverter protocol
3: Metasys N2 protocol
5: BACnet protocol
50: Communications link pump control protocol
Y Y 0
y95 Data Clear Processing for Communications
Error
0: Do not clear the data of function codes Sxx when a
communications error occurs. (compatible with the
conventional inverters)
1: Clear the data of function codes S01/S05/S19 when a
communications error occurs.
2: Clear the run command assigned bit of function code S06
when a communications error occurs.
3: Clear both data of S01/S05/S19 and run command assigned
bit of S06 when a communications error occurs.
* Related alarms: Er8, ErP, Er4, Er5, ErU
Y Y 0
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...