6-226
Slow flowrate stop function (Cancel deviation level 1) (J158, J258)
Set a cancel deviation level to be used as a cancel condition. Set PID control 1 and PID
control 2 with function codes J158 and J258 respectively.
- Data setting range: 0.01 to 9990.00, OFF
Slow flowrate stop function (Cancel delay timer) (J159, J259)
Set time delay from satisfaction of slow flowrate's cancel conditions (J157, J257) until
initiation of the inverter. Set PID control 1 and PID control 2 with function codes J159 and
J259 respectively.
- Data setting range: 0 to 3600 (s)
Slow flowrate stop function (Cancel deviation level 2) (J160, J260)
In a case where water supply is needed until the initiation inhibition time (J156, J256) elapses,
set a cancel deviation level as a cancel (initiation) condition for water stoppage prevention.
Set PID control 1 and PID control 2 with function codes J160 and J260 respectively.
Set a value so that the following is resulted: cancel deviation level 1 (J158, J258) < cancel
deviation level 2 (J160, J260).
If a value is set so that the cancel deviation level 1 (J158, J258) exceeds the cancel deviation
level 2 (J160, J260), the cancel deviation level 2 (J160, J260) is used as the cancel condition
even when the initiation inhibition time (J156, J256) elapses.
- Data setting range: 0.01 to 9990.00, OFF
Assignment of PID-STP ("Motor stopped due to slow flowrate under PID control")
(function codes E20 to E24 and E27, data = 44)
With respect to PID slow flowrate stop, ON signals are output when the inverter stops due to
the slow flowrate during PID control. When signals which indicate inverter stop status are
needed, PID-STP has to be assigned.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...