6-142
6.3.4
P codes (Motor 1 parameters)
To use the integrated automatic control functions such as auto torque boost, torque calculation
monitoring, torque limiter, automatic deceleration (anti-regenerative control), auto search for idling
motor speed, slip compensation, and torque vector control, it is necessary to build a motor model in the
inverter by specifying proper motor parameters including the motor capacity and rated current.
P01
Motor 1 (No. of poles)
P01 specifies the number of poles of the motor. Enter the value given on the nameplate of the
motor. This setting is used to display the motor speed on the LCD monitor and to control the
speed (refer to E43). The following expression is used for the conversion.
(Hz)
Frequency
×
poles
of
No.
120
(r/min)
speed
Motor
=
- Data setting range: 2 to 22 (poles)
P02
Motor 1 (Rated capacity)
P02 specifies the rated capacity of the motor. Enter the rated value given on the nameplate of
the motor.
Data for P02
Unit
Dependency on function code P99
kW
When P99 (Motor 1 Selection) = 0 or 4
0.01 to
1000.00
HP
When P99 (Motor 1 Selection) = 1
When accessing P02 with the keypad, take into account that the P02 data automatically
updates data of P03, P06 through P12, and H46.
P03
Motor 1 (Rated current)
P03 specifies the rated current of the motor. Enter the rated value given on the nameplate of
the motor.
- Data setting range: 0.00 to 2000.00 (A)
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...