6-24
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
J504 External PID Control 1
(Deviation
selection)
0: (J5-02) - (J5-03)
51: Maximum (Maximum deviation between external PID control
1 and 2)
52: Minimum (Minimum deviation between external PID control 1
and 2)
N Y 0
J505
(Display unit) 0: Based on the unit/scale of the PID control 1 feedback amount
1: none
2: %
4: r/min
7: kW
Flowrate
20: m
3
/s
21: m
3
/min
22: m
3
/h
23: L/s
24: L/min
25: L/h
Pressure
40: Pa
41: kPa
42: MPa
43: mbar
44: bar
45: mmHg
46: psi (Pound per square inch)
47: mWG
48: inWG
Temperature
60: K
61: °C
62: °F
Density
80: ppm
N Y 0
J506
(Maximum scale) -999.00 to 0.00 to 9990.00
N Y
100.00
J507
(Minimum scale) -999.00 to 0.00 to 9990.00
N Y
0.00
J510
P (Gain) 0.000 to 30.000 times
ON/OFF: ON/OFF control
Y Y
0.100
J511
I (Integral time) 0.0 to 3600.0 s
Y Y 0.0
J512
D (Differential time) 0.00 to 600.00 s
Y Y
0.00
J513
(Feedback filter) 0.0 to 900.0 s
Y Y 0.5
J514
(Anti-reset
wind-up) OFF:
Disable
0.00 to 9990.00 *10
Y Y
OFF
J515
(ON/OFF control hysteresis width) 0.00 to 9990.00 *10
Y Y
0.00
J516
(Proportional operation output convergent
value)
0 to 150%
Y Y 0
J517
(Proportional cycle) 1 to 150 s
Y Y 30
J518
(Upper limit of PID process output) -10 to +110%
Y Y 100
J519
(Lower limit of PID process output) -10 to +110%
Y Y 0
J520
(Upper and lower limits) 0: Limit PID output with J518, J519
1: 110%, -10% of PID output with J518 exceeded or less than
J519
Y Y 0
J521
(Alarm output selection) 0: Absolute-value alarm (PV)
1: Absolute-value alarm (PV) (with Hold)
2: Absolute-value alarm (PV) (with Latch)
3: Absolute-value alarm (PV) (with Hold and Latch)
4: Deviation alarm (PV)
5: Deviation alarm (PV) (with Hold)
6: Deviation alarm (PV) (with Latch)
7: Deviation alarm (PV) (with Hold and Latch
8: Absolute-value alarm (SV)
9: Absolute-value alarm (SV) (with Hold)
10: Absolute-value alarm (SV) (with Latch)
11: Absolute-value alarm (SV) (with Hold and Latch)
12: Absolute-value alarm (MV)
13: Absolute-value alarm (MV) (with Hold)
14: Absolute-value alarm (MV) (with Latch)
15: Absolute-value alarm (MV) (with Hold and Latch)
Y Y 0
*10 The upper and lower level values are restricted by the maximum and minimum scales.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...