6-84
F43, F44
Current Limiter (Mode selection and Level)
H12 (Instantaneous Overcurrent Limiting, Mode selection)
When the output current of the inverter exceeds the level specified by the current limiter
(F44), the inverter automatically manages its output frequency to prevent a stall and limits the
output current. The default of the current limiter level is 120%. Do not change the factory
default except when necessary.
The current limiter mode is selected with F43. If F43 = 1, the current limiter is enabled only
during constant speed operation. If F43 = 2, it is enabled during both of acceleration and
constant speed operation. Choose F43 = 1 if you need to run the inverter at full capability
during acceleration and to limit the output current during constant speed operation.
Mode selection (F43)
F43 selects the motor running state in which the current limiter becomes activated.
Running states that enable the current limiter
Data for
F43
During acceleration
During constant speed
During deceleration
0 Disable
Disable
Disable
1 Disable
Enable Disable
2
Enable
Enable Disable
Level (F44)
F44 specifies the operation level at which the output current limiter becomes activated, in
ratio to the inverter rating.
- Data setting range: 20 to 120 (%) (in ratio to the inverter rating)
Instantaneous Overcurrent Limiting (Mode selection) (H12)
H12 specifies whether the inverter invokes the current limit processing or enters the
overcurrent trip when its output current exceeds the instantaneous overcurrent limiting level.
Under the current limit processing, the inverter immediately turns OFF its output gate to
suppress the further current increase and continues to control the output frequency.
Data for H12
Function
0
Disable
An overcurrent trip occurs at the instantaneous overcurrent limiting level.
1 Enable
If any problem could occur when the motor torque temporarily drops during current limiting
processing, it is necessary to cause an overcurrent trip (H12 = 0) and actuate a mechanical
brake at the same time.
• Since the current limit operation with F43 and F44 is performed by software, it
may cause a delay in control. If you need a quick response current limiting, also
enable the instantaneous overcurrent limiting with H12.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...