6.2 Function Code Tables
6-25
Chap. 6
FUNCTION C
ODES
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
J522 External PID Control 1
(Upper level alarm (AH))
-999.00 to 0.00 to 9990.00 *10
OFF
Y Y
OFF
J524
(Lower level alarm (AL)) -999.00 to 0.00 to 9990.00 *10
OFF
Y Y
OFF
J527
(Feedback error detection mode) 0: Disable (Turns ON output signals (EPV1-ERR) and continues
operation.)
1: Enable (Free run stop (PVA trip))
2: Enable (Deceleration and stop (PVA trip))
Y Y 0
J529
(Feedback error upper-limit) -999.00 to 0.00 to 9990.00 *10
Auto: 105% equivalent
Y Y
Auto
J530
(Feedback error lower-limit) -999.00 to 0.00 to 9990.00 *10
Auto: -5% equivalent
Y Y
Auto
J531
(Feedback error detection time) 0.0 to 300.0 s
Y Y 0.1
J540
(Manual
command) 0: Keypad
( / key)
8: Keypad
( / key) (Balanceless-bumpless)
51: External PID command 1 (Analog input: Terminals [12], [C1]
and [V2])
N Y 0
J550 External PID Multistep Command
(Mode
selection)
Bit 0: Enable multistep command under external PID control 1
Bit 1: Enable multistep command under external PID control 2
Bit 2: Enable multistep command under external PID control 3
N Y 0
J551
(Multistep command 1) -999.00 to 0.00 to 9990.00
Y Y
0.00
J552
(Multistep command 2) -999.00 to 0.00 to 9990.00
Y Y
0.00
J553
(Multistep command 3) -999.00 to 0.00 to 9990.00
Y Y
0.00
J6 codes: External PID Function 2/3
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
J601 External PID Control 2
(Mode selection) 0: Disable
1: Enable process control (Normal operation)
2: Enable process control (Inverse operation)
11: Enable process control, interlocking with inverter running
(Normal operation)
12: Enable process control, interlocking with inverter running
(Inverse operation)
21: Enable process control by external digital signal (Normal
operation)
22: Enable process control by external digital signal (Inverse
operation)
31: Enable process control by external digital signal, interlocking
with inverter running (Normal operation)
32: Enable process control by external digital signal, interlocking
with inverter running (Inverse operation)
N Y 0
J602
(Remote
command
selection)
0: Keypad
( / key)
3:
UP
/
DOWN
4: Command via communications link
51: External PID command 1 (Analog input terminals [12], [C1]
and [V2])
52: External PID command 2 (Analog input terminals [12], [C1]
and [V2])
111: Apply external PID control 1 commands
N Y 0
J603
(Feedback selection) 51: External PID feedback value 1
52: External PID feedback value 2
N Y 52
*10 The upper and lower level values are restricted by the maximum and minimum scales.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...