6.3 Details of Function Codes
6-135
Chap. 6
FUNCTION C
ODES
Note:
Entry of a reverse rotation command with the
key or terminal [REV] cancels the
run command and produces no inverter operation. The rotation direction should be specified
by the data of C21 to C28.
Note:
When an pattern operation is commanded via input terminals, the self-hold function of
a run command does not work. Use an alternate switch if necessary.
Note:
After completion of a cycle of pattern operation, the inverter decelerates to a stop with
the deceleration time specified by F08 (Deceleration time 1).
C30
Frequency Command 2
(Refer to F01.)
For details of frequency command 2, refer to the description of F01.
C31 to C35
C36 to C39
C41 to C45
C40
Analog Input Adjustment for [12]
(Offset, Gain, Filter time constant, Gain base point, Polarity)
Analog Input Adjustment for [C1]
(Offset, Gain, Filter time constant, Gain base point)
Analog Input Adjustment for [V2]
(Offset, Gain, Filter time constant, Gain base point, Polarity)
Terminal [C1] Input Range Selection
F01 (Frequency Command 1)
Setting up a reference frequency using analog input
You can adjust the gain, polarity, filter time constant, and offset which are applied to analog
inputs (voltage inputs to terminals [12] and [V2], and current input to terminal [C1]).
Adjustable items for analog inputs
Gain
Input
terminal Input range
Gain Base
point
Polarity Filter time
constant
Offset Terminal [C1]
input range
[12]
0 to +10 V,
-10 to +10 V
C32 C34 C35 C33 C31
⎯
[C1]
4 to 20 mA
C37
C39
⎯
C38 C36 C40
[V2]
0 to +10 V,
-10 to +10 V
C42 C44 C45 C43 C41
⎯
Offset (C31, C36, C41)
C31, C36 or C41 configures an offset for an analog voltage/current input. The offset also
applies to signals sent from the external equipment.
- Data setting range: -5.0 to +5.0 (%)
Filter time constant (C33, C38, C43)
C33, C38 or C43 configures a filter time constant for an analog voltage/current input. The
larger the time constant, the slower the response. Specify the proper filter time constant
taking into account the response speed of the machine (load). If the input voltage fluctuates
due to line noises, increase the time constant.
- Data setting range: 0.00 to 5.00 (s)
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...