6-290
J506
J507
External PID Control 1 (Maximum scale, Minimum scale)
J606, J607 (External PID Control 2 (Maximum scale, Minimum scale))
J656, J657 (External PID Control 3 (Maximum scale, Minimum scale))
J506/J507, J606/J607, or J656/J657 specify the maximum/minimum scale for external PID
control 1, 2 or 3, respectively.
Set the maximum scale "External PID command value / Display value at 100% of external
PID feedback value" with J506/J606/J656, and the minimum scale "External PID command
value / Display value at 0% of external PID feedback value" with J507/J607/J657.
Display values are calculated with the following expression.
Display value =
(External PID control value (%)) / 100 x (Maximum scale - Minimum scale) + Minimum scale
- Data setting range: (Maximum scale and minimum scale) -999.00 to 0.00 to 9990.00
When external PID control is to be performed with the same unit and scale as for
feedback values, the J506/J606/J656 or J507/J607/J657 settings need not be
changed. (Factory default: In accordance with the unit and scale used for feedback
values. Refer to J505/J605/J655.)
Configure the J506/J606/J656 and J507/J607/J657 to use different unit and scale
from feedback values.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...