6.2 Function Code Tables
6-23
Chap. 6
FUNCTION C
ODES
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
J459 Motor Decrease Switching Level
0 to 100%, Inherit
Inherit: Depends on J456
Y Y
Inherit
J460 Motor Decrease PID Control Start
Frequency
0 to 120 Hz, Inherit
Inherit: Depends on J450
Y Y
Inherit
J461 Motor Increase/Decrease Switching
Judgment Non-responsive Area Width
OFF, 0.1 to 50.0%
OFF: Disable
0.1 to 50.0%
Y Y
OFF
J462 Failure Inverter Judgment Time
OFF, 0.5 to 600.0 s
Y Y 5.0
J465 Auxiliary
Motor
(Frequency operation level)
0.1 to 120.0 Hz
OFF: Disable
Y Y
50.0
J466
(Hysteresis width) 0.0 to 120.0 Hz
Y Y 1.0
J467
(PV operation level) 0.01 to 9990.00 *10
OFF: Disable
Y Y
OFF
J468
(Connection timer) 0.00 to 2.00 s
Y Y
0.00
J469
(Interrupting timer) 0.00 to 2.00 s
Y Y
0.00
J480 Motor Cumulative Run Time
(Motor 0)
Y N 0
J481
(Motor
1)
0 to 65535
For adjustment at the replacement time
J482
(Motor
2)
J483
(Motor
3)
J484
(Motor
4)
J485
(Motor
5)
J486
(Motor
6)
J487
(Motor
7)
J488
(Motor
8)
J490 Y Terminal ON Maximum Cumulation Count
(Y1
Y2)
J491
(Y3
Y4)
J492 Relay ON Maximum Cumulation Count
(Y5A
30AB)
J493
(Y6RY to Y12RY)
0.000 to 9999
(The display of "1.000" indicates 1000 times.)
Y N
0.000
J5 codes: External PID Function 1
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
J501 External PID Control 1
(Mode selection) 0 Disable
1: Enable process control (Normal operation)
2: Enable process control (Inverse operation)
11: Enable process control, interlocking with inverter running
(Normal operation)
12: Enable process control, interlocking with inverter running
(Inverse operation)
21: Enable process control by external digital signal (Normal
operation)
22: Enable process control by external digital signal (Inverse
operation)
31: Enable process control by external digital signal, interlocking
with inverter running (Normal operation)
32: Enable process control by external digital signal, interlocking
with inverter running (Inverse operation)
N Y 0
J502
(Remote command selection) 0: Keypad ( / key)
3:
UP
/
DOWN
4: Command via communications link (Use function code S13)
51: External PID command 1 (Analog input: Terminals [12], [C1]
and [V2])
N Y 0
J503
(Feedback selection) 51: External PID feedback value 1
60: Addition (External PID feedback value 1 + External PID
feedback value 2)
61: Difference External PID feedback value 1 - External PID
feedback value 2)
62: Average (External PID feedback value 1, External PID
feedback value 2)
63: Maximum (External PID feedback value 1, External PID
feedback value 2)
64: Minimum (External PID feedback value 1, External PID
feedback value 2)
N Y 51
*10 The upper and lower level values are restricted by the maximum and minimum scales.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...