Current detected --
ID
When the inverter output current exceeds the level specified by E34 for the period specified
by E35, the
ID
signal turns ON, respectively. When the output current drops below 90% of
the rated operation level, the
ID
turns OFF. (The minimum ON-duration is 100 ms.)