3-4
(1) Calculating the load torque during constant speed running (For detailed calculation,
refer to Section 3.1.3.1)
It is essential to calculate the load torque during constant speed running for all loads.
First calculate the load torque of the motor during constant speed running and then select a
tentative capacity so that the continuous rated torque of the motor during constant speed running
becomes higher than the load torque. To perform capacity selection efficiently, it is necessary to
match the rated speeds (base speeds) of the motor and load. To do this, select an appropriate
reduction-gear (mechanical transmission) ratio and the number of motor poles.
If the acceleration or deceleration time is not restricted, the tentative capacity can apply as a
defined capacity.
(2) Calculating the acceleration time (For detailed calculation, refer to Section 3.1.3.2)
When there are some specified requirements for the acceleration time, calculate it according to
the following procedure:
1) Calculate the total moment of inertia for the load and motor
Calculate the moment of inertia for the load, referring to Section 3.1.3.2, "Calculation of
acceleration/deceleration time." For the motor, refer to the related motor catalogs. Sum them
up.
2)
Calculate the required minimum acceleration torque (See Figure 3.4)
The acceleration torque is the difference between the motor short-time output torque (base
frequency: 60 Hz) explained in Section 3.1.1 (2), "Maximum driving torque in a short time"
and the load torque (
τ
L
/
η
G
) during constant speed running calculated in the above (1).
Calculate the required minimum acceleration torque over the whole range of speed.
3) Calculate the acceleration time
Assign the value calculated above to the equation (3.10) in Section 3.1.3.2, "Calculation of
acceleration/deceleration time" to calculate the acceleration time. If the calculated
acceleration time is longer than the expected time, select the inverter and motor having one
class higher capacity and calculate it again.
Figure 3.4 Example Study of Minimum Acceleration Torque
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...