6-8
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
E30 Frequency Arrival
(Hysteresis width) 0.0 to 10.0 Hz
Y Y 2.5
E31 Frequency Detection 1
(Level) 0.0 to 120.0 Hz
Y Y
50.0
E32
(Hysteresis width) 0.0 to 120.0 Hz
Y Y 1.0
E34 Overload Early Warning/Current Detection
(Level)
OFF: Disable
1 to 150% of inverter rated current
Y Y1 *3
E35
(Timer) 0.01
to
600.00s
Y Y
10.00
E61 Terminal [12] Extended Function
N Y 0
E62 Terminal [C1] Extended Function
N Y 0
E63 Terminal [V2] Extended Function
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID process command 1
4: PID process command 2
5: PID feedback value 1
12: Acceleration/deceleration time ratio setting
13: Upper limit frequency
14: Lower limit frequency
20: Analog signal input monitor
30: PID feedback value 2
31: Auxiliary input 1 to PID process command
32: Auxiliary input 2 to PID process command
33: Flow sensor
41: External PID process command 1
42: External PID feedback value 1
43: External PID manual command 1
44: External PID process command 2
45: External PID feedback value 2
46: External PID manual command 2
47: External PID process command 3
48: External PID feedback value 3
49: External PID manual command 3
N Y 0
E64 Saving of Digital Reference Frequency
0: Automatic saving (when main power is turned OFF)
1: Saving by pressing key
Y Y 1
E65 Reference Loss Detection
(Continuous
running
frequency)
OFF: Cancel
Decel: Decelerate to stop
20% to 120%
Y Y
OFF
E80 Low Torque Detection
(Level) 0% to 150%
Y Y 20
E81
(Timer) 0.01 to 600.00 s
Y Y
20.00
E82 Switching Frequency of Accel/Decel Time
in Low-Speed Domain
Inherit: Follow the setting of F16
0.1 to 120.0 Hz
Y Y
Inherit
E83 Acceleration Time in Low-Speed Domain
Inherit: Follow the current acceleration time
0.01 to 3600.00 s: Acceleration time from 0 Hz to E82
Y Y
Inherit
E84 Deceleration Time in Low-Speed Domain
Inherit: Follow the current deceleration time
0.01 to 3600.00 s: Deceleration time from E82 to 0 Hz
Y Y
Inherit
E85 Gradual
Deceleration
Time
Switching
Frequency
OFF: Disable
0.1 to 120.0 Hz
Y Y
OFF
E86 Gradual
Deceleration
Time
(Check
valve
protection)
Inherit: Follow the current deceleration time
0.01 to 3600.00 s: Deceleration time from E82 to E85
Y Y
Inherit
*3 The motor parameters are set by capacities. See Table B (function code P03).
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...