6-78
When the variable torque V/f pattern is selected (F37 = 0 or 3), the output voltage
may be low at a low frequency zone, resulting in insufficient output torque,
depending on the characteristics of the motor and load. In such a case, it is
recommended to increase the output voltage at the low frequency zone using the
non-linear V/f pattern.
Recommended value: H50 = 1/10 of the base frequency
H51 = 1/10 of the voltage at base frequency
Torque boost
•
Manual torque boost (F09)
- Data setting range: 0.0 to 20.0 (%), (100%/Rated voltage at base frequency)
In torque boost using F09, constant voltage is added to the basic V/f pattern, regardless of the
load. To secure a sufficient starting torque, manually adjust the output voltage to optimally
match the motor and its load by using F09. Specify an appropriate level that guarantees
smooth start-up and yet does not cause over-excitation at no or light load.
Torque boost using F09 ensures high driving stability since the output voltage remains
constant regardless of the load fluctuation.
Specify the F09 data in percentage to the rated voltage at base frequency 1 (F05). At factory
shipment, F09 is preset to a level that assures approx. 50% of starting torque.
• Specifying a high torque boost level will generate a high torque, but may cause
overcurrent due to over-excitation at no load. If you continue to drive the motor,
it may overheat. To avoid such a situation, adjust torque boost to an appropriate
level.
• When the non-linear V/f pattern and the torque boost are used together, the
torque boost takes effect below the frequency on the non-linear V/f pattern’s
point.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...