6.3 Details of Function Codes
6-181
Chap. 6
FUNCTION C
ODES
In addition, during deceleration triggered by turning the run command OFF, anti-regenerative
control increases the output frequency so that the inverter may not stop the load depending on
the load state (huge moment of inertia, for example). To avoid that, H69 provides a choice of
cancellation of anti-regenerative control to apply when three times the specified deceleration
time is elapsed, thus decelerating the motor forcibly.
Function
Data for H69
Control mode
Force-to-stop with actual
deceleration time exceeding three
times the specified one
0
Disable automatic deceleration
―
2
Torque limit control
Enable
3
DC link bus voltage control
Enable
4
Torque limit control
Disable
5
DC link bus voltage control
Disable
Torque Limiter for braking (Frequency increment limit) (H76)
- Data setting range: 0.0 to 500.0 (Hz)
Since increasing the output frequency too much in the torque limit control mode is dangerous,
the inverter has a torque limiter (Frequency increment limit for braking) that can be specified
by H76. The torque limiter limits the inverter's output frequency to less than "Reference
fre H76 setting."
Note that the torque limiter activated restrains the anti-regenerative control, resulting in an
overvoltage trip in some cases. Increasing the H76 data improves the anti-regenerative
control capability.
Automatic deceleration (Operation level) (H114)
- Data setting range: Auto, 0.0 to 50.0 (%)
H114 specifies the anti-regenerative control operation level under torque limit control. The
inverter controls the output frequency to keep the braking torque at the value specified with
H114. When H114 = Auto (factory default), the anti-regenerative control starts with the
inverter internal fixed value (approx. 2% to 5%). Do not change the factor default except
when necessary.
• Enabling the automatic deceleration (anti-regenerative control) may
automatically increase the deceleration time.
• If the set deceleration time is too short, the DC link bus voltage of the inverter
rises quickly, and consequently, the automatic deceleration may not follow the
voltage rise. If this is the case, set longer deceleration time.
H70
Overload Prevention Control
H70 specifies the decelerating rate of the output frequency to prevent a trip from occurring
due to an overload. This control decreases the output frequency of the inverter before the
inverter trips due to a heat sink overheat or inverter overload (with an alarm indication of
OH1 or OLU, respectively). It is useful for equipment such as pumps where a decrease in the
output frequency leads to a decrease in the load and it is necessary to keep the motor running
even when the output frequency drops.
Data for H70
Function
Inherit
Decelerate the motor with the preset deceleration time
0.01 to 100.0 Decelerate the motor by deceleration rate from 0.01 to 100.0 (Hz/s)
OFF
Cancel overload prevention control
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...