6-86
6.3.2
E codes (Extension terminal functions)
E01 to E07
Terminal [X1] to [X7] Functions
E98 and E99 (Terminal [FWD] and [REV] Functions)
E01 to E07, E98 and E99 assign commands (listed below) to general-purpose, programmable,
digital input terminals, [X1] to [X7], [FWD], and [REV].
These function codes can also switch the logic system between normal and negative to define
how the inverter logic interprets the ON or OFF state of each terminal. The factory default
setting is normal logic system "Active ON." So, descriptions that follow are given in normal
logic system. They are, in principle, arranged in the numerical order of assigned data.
However, highly relevant signals are collectively described where one of them first appears.
Refer to the function codes in the "Related function codes" column, if any.
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward"
FWD
and "Fire mode"
FMS
), stop commands (e.g.,
"Coast to a stop"
BX
), and frequency change commands can be assigned to digital input
terminals. Depending upon the assignment states of those terminals, modifying the function
code setting may cause a sudden motor start or an abrupt change in speed.
• When the inverter is controlled with the digital input signals, switching run or frequency
command sources with the related terminal commands (e.g.,
SS1
,
SS2
,
SS4
,
SS8
,
Hz2/Hz1
,
Hz/PID
,
IVS
,
LE
and
FMS
) may cause a sudden motor start or an abrupt change in speed.
An accident or physical injury may result.
Function code data
Active
ON
Active
OFF
Terminal commands assigned
Symbol
Related
function
codes
0 1000
SS1
1 1001
SS2
2 1002
SS4
3 1003
Select multistep frequency
(0 to 15 steps)
SS8
C05 to C19
4
1004
Select ACC/DEC time (2 steps)
RT1
5
1005
Select ACC/DEC time (4 steps)
RT2
F07, F08,
E10 to E15
6 1006
Enable
3-wire
operation
HLD
F02
7
1007
Coast to a stop
BX
⎯
8 1008
Reset
alarm
RST
⎯
1009
9
Enable external alarm trip
THR
⎯
11
1011
Select frequency command 2/1
Hz2/Hz1
F01, C30
13
⎯
Enable
DC
braking
DCBRK
F20 to F22
14
1014
Select torque limiter level 2/1
TL2/TL1
F40, F41, E16,
E17
15
⎯
Switch to commercial power (50 Hz)
SW50
⎯
16
⎯
Switch to commercial power (60 Hz)
SW60
⎯
17
1017
UP (Increase output frequency)
UP
Frequency
setting:
F01, C30
18
1018
DOWN (Decrease output frequency)
DOWN
PID command:
J101, J201
19
1019
Enable data change with keypad
WE-KP
F00
20
1020
Cancel PID control
Hz/PID
J101 to J131
J201 to J231
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...