Inverter's function codes dedicated to CC-Link communication
Function
code
Function
Data setting
range *
1
Description
y98 Select
run/frequency
command sources
0 to 3
Select from the following choices:
y98
Frequency
command source
Run command
source
0 Inverter Inverter
1 CC-Link Inverter
2 Inverter CC-Link
3 CC-Link CC-Link
0, 4 to 9
Immediately coast to a stop and trip with Er5.
1
After the time specified by o28, coast to a stop
and trip with Er5.
2
If the communications link is restored within
the time specified by o28, ignore the
communications error. If a timeout occurs,
coast to a stop and trip with Er5.
3, 13 to 15
Keep the current operation, ignoring the
communications error. (No Er5 trip occurs.)
10 Immediately
decelerate
to a stop. Issue Er5
after stopping.
11
After the time specified by o28, decelerate to a
stop. Issue Er5 after stop.
o27
Select error processing for
CC-Link network breaks
12
If the communications link is restored within
the time specified by o28, ignore the
communications error. If a timeout occurs,
decelerate to a stop and trip with Er5.
o28
Set the operation timer to
be used in error processing
for network breaks
0.0 to 60.0 sec. Applies when o27 = 1, 2, 11, or 12
5 to 255
No operation
0, 1
1 station occupied
(CC-Link version 1.10)
2
1 station occupied, 2X setting
(CC-Link version 2.00)
3
1 station occupied, 4X setting
(CC-Link version 2.00)
o30 CC-Link
extension
4
1 station occupied, 8X setting
(CC-Link version 2.00)
o31 Station
address
*
2
0, 1 to 64
Any of 1 to 64 should be specified for a slave
station.
Specifying any other value causes the L.ERR
LED to light.
o32
Transmission speed *
2
0 to 4
0: 156 kbps, 1: 625 kbps, 2: 2.5 Mbps,
3: 5 Mbps, 4: 10 Mbps
Specifying any other value causes the L.ERR
LED to light.
*
1 The underlined values are factory defaults.
*
2 If the station address (o31) or the transmission speed (o32) is modified when the inverter power is ON, the L.ERR
LED flashes and the communications link is lost. Turning the terminal command
RST
ON or restarting both the
inverter and the communications card validates the new setting.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...