5.7 Alarm Mode
5-99
Chap. 5
PR
EP
AR
A
T
IO
N AND
TEST
RUN
5) Calibrating the [FM1] / [FM2] output
Calibrate the full scale of the analog meter connected to the terminals [FM1] and [FM2], using
the reference voltage equivalent to +10 VDC or current equivalent to 20 mA. To output the
reference voltage, it is necessary to select the analog output test with the function code
(F31/F35 = 14).
6) Clearing the alarm history
Clear the alarm history saved during the system setup with the function code (H97 = 1).
Depending upon the situation of the practical operation, it may become necessary to modify
the settings of the torque boost (F09) and acceleration/deceleration times (F07/F08). Confirm
the function code data and modify them properly.
The inverter is available in either remote or local mode.
• Remote mode: The inverter is driven by terminal commands, via the communications link
or from the keypad which are selectable with function codes.
• Local mode: The inverter is separated from the system and driven by keypad operation.
This mode is convenient for test-run and maintenance.
For details, refer to Section 5.5.4 "Remote and local modes."
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...