6.3 Details of Function Codes
6-251
Chap. 6
FUNCTION C
ODES
< Function code configuration required for the inverter drive motor floating system and the
inverter drive motor fl commercial power-driven motor system >
(1) Function codes to be configured
Function code
Name
Data
Description
J401 Pump
control
mode selection
2: Inverter drive motor
floating system
3: Inverter drive motor
fl
commercial
power-driven motor
system
J101 to J138
J201 to J231
PID control 1
PID control 2
Depends on each code
setting
These function codes configure PID control in
accordance with the system design.
PID1/PID2 switchable.
E20 to E27
o01 to o07
[Y1] to [Y5]
[30A/B/C]
[Y6] to [Y12]
88:
AUX_L
(Auxiliary
motor drive signal)
160 to 166:
M1_l
to
M4_l
(Motor 1 to 4
being driven by
inverter)
161 to 167:
M1_L
to
M4_L
(Motor 1 to 4
being driven by
commercial power)
These function codes assign inverter drive start
signals and commercial drive start signals to
the output terminals according to the number
of pumps.
For a maximum configuration, the optional
relay output card is required.
AUX_L
is a drive signal for auxiliary pump.
J411 to J414 Motor 1 to
Motor 4 mode
selection
1: Enable
These function codes configure motor modes
according to the number of pumps.
Only motors enabled can be control targets.
(2) Function codes recommended to be configured
Function code
Name
Data
Description
J425 Motor
switching
procedure
1: Equal operating time This function code automatically adjusts the
start/stop sequence of commercial
power-driven pumps to equalize the operating
times of pumps.
(3) Function codes for individual adjustments
Configure the following function codes as needed.
Function code
Name
Data
Description
J450 Motor
increase
judgment
(Judgment
frequency)
0 to 120 Hz, Inherit
J451 Motor
increase
judgment
(Duration time)
0.00 to 3600 s
This function code adjusts the motor adding
conditions.
If the frequency of the inverter-driven pump
exceeds the setting of J450 and keeps it for the
setting of J451, commercial power-driven
motor adding conditions are met.
The default is that if the frequency reaches the
setting of J118 (PID upper limiter), the adding
conditions are immediately met.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...