2-20
2.3.2
Setting up the slide switches
Before changing the switches, turn OFF the power and wait at least ten minutes. Make sure that the LCD
monitor is turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link
bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below).
An electric shock may result if this warning is not heeded as there may be some residual electric
charge in the DC bus capacitor even after the power has been turned OFF.
Switching the slide switches located on the control PCB allows you to customize the operation mode
of the analog output terminals, digital I/O terminals, and communications ports. The locations of those
switches are shown in Figure 2.11.
To access the slide switches, remove the front cover so that you can see the control PCB.
Table 2.1 lists the function of each slide switch.
Table 2.1 Function of Each Slide Switch
Slide Switch
Function
SW1
Switches the service mode of the digital input terminals between SINK and SOURCE.
- This switches the input mode of digital input terminals [X1] to [X7], [FWD] and
[REV] to be used as the SINK or SOURCE mode.
- Factory default: SINK
SW2
Switches the terminating resistor of RS-485 communications port on the inverter ON
and OFF. (RS-485 communications port 2, on the terminal block)
- If the inverter is connected to the RS-485 communications network as a terminating
device, turn SW2 to ON.
SW3
Switches the terminating resistor of RS-485 communications port on the inverter ON
and OFF. (RS-485 communications port 1, for connecting the keypad)
- To connect a keypad to the inverter, turn SW3 to OFF (Factory default).
- If the inverter is connected to the RS-485 communications network as a terminating
device, turn SW3 to ON.
SW4/SW6
Switches the output mode of the analog output terminal [FM1]/[FM2] between voltage
and current.
When changing this switch setting, also change the data of function code F29/F32.
[FM1] [FM2]
SW4
F29 data
SW6
F32 data
Voltage output (Factory default)
VO1
0
VO2
0
Current output
IO1
1, 2
IO2
1, 2
SW5
Switches the property of the analog input terminal [C1] between analog setting current
input and PTC thermistor input.
When changing this switch setting, also change the data of function code H26.
SW5 H26
data
Analog setting current input
(Factory default)
C1 0
PTC thermistor input
PTC
1 (alarm) or 2 (warning)
Output mode
Output mode
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...