A-14
[ 2 ] Suppressing surge voltages
There are two ways for suppressing the surge voltages, one is to reduce the voltage rise time and
another is to reduce the voltage peak value.
(1) Output reactor
If wiring length is relatively short, the surge voltages can be suppressed by reducing the voltage rise
time (dv/dt) with the installation of an AC reactor on the output side of the inverter. (Refer to Figure
B.3 (1).)
However, if the wiring length becomes long, suppressing the peak voltage due to surge voltage may
be difficult.
(2) Output filter
Installing a filter on the output side of the inverter allows a peak value of the motor terminal voltage
to be reduced. (Refer to Figure B.3 (2).)
(1) Output reactor
(2) Output filter
Figure B.3 Method to Suppress Surge Voltage
If the wiring length between the inverter and the motor is comparatively long, the crest
value of the surge voltage can be suppressed by connecting a surge suppressor unit (SSU)
to the motor terminal. For details, refer to Chapter 4, Section 4.4.1.3 "Surge suppression
unit (SSU)."
[ 3 ] Using motors with enhanced insulation
Enhanced insulation of a motor winding allows its surge withstanding to be improved.
B.4 Regarding existing equipment
[ 1 ] In case of a motor being driven with 400 V class inverter
A survey over the last five years on motor insulation damage due to the surge voltages originating
from switching of inverter elements shows that the damage incidence is 0.013% under the surge
voltage condition of over 1,100 V and most of the damage occurs several months after
commissioning the inverter. Therefore there seems to be little probability of occurrence of motor
insulation damage after a lapse of several months of commissioning.
[ 2 ] In case of an existing motor driven using a newly installed 400 V class inverter
We recommend suppressing the surge voltages with the ways shown in Section B.3.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...