6-254
Mutual operation control (Communications-linked inverter drive motor floating system)
This system controls up to three pumps which are individually connected with the FRENIC-AQUA
units in multidrop connection via RS-485.
The FRENIC-AQUA specified as a master performs PID control and sends run commands and
frequency commands to other two slaves.
If the frequency rises due to a PV signal level drop to satisfy the pump adding conditions, the second
inverter is started. After the start of a total of three inverters, the master can output a start signal to
drive an auxiliary pump. The start/stop sequence of pumps cycles.
Even if the master stops due to an alarm, the slaves can continue running.
The advantage of this system is very small pressure fluctuation at the time of adding/subtracting
pumps and small load to piping since all pumps are driven by inverters. The disadvantage is high cost
since each pump requires an inverter.
Mutual operation control (Communications-linked all motors simultaneous PID control
system)
This system is configured in the same way as the communications-link inverter drive motor floating
system except that all motors are driven under PID control with the same frequency at the same time.
Even if an alarm occurs, the remaining inverters continue to run. If the pressure is insufficient, the
inverter outputs a start signal to an auxiliary pump to add one pump.
The advantage of this system is that driving two or more pumps under PID control at the same time can
deliver water with low power for optimum watt hour in the cooling water cycling system managing the
flowrate.
< Maximum number connection configuration of mutual operation (J401 = 52 or 54) >
L1/R
L2/S
L3/T
U
V
W
Acc./Dec.
controller
PID
Command
M0
Pump
Pressure sensor
Feedback
L1/R
L2/S
L3/T
U
V
W
Acc./Dec.
controller
Command
M0
Pump
L1/R
L2/S
L3/T
U
V
W
Acc./Dec.
controller
Command
M0
Pump
RTU communication
PID
control
DX+/DX-
DX+/DX-
DX+/DX-
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...