6.3 Details of Function Codes
6-65
Chap. 6
FUNCTION C
ODES
Restart mode after momentary power failure (Allowable momentary power failure time)
(H16)
H16 specifies the maximum allowable duration (0.0 to 30.0 seconds) from an occurrence of a
momentary power failure (undervoltage) until the restart of the inverter. Specify the
coast-to-stop time during which the machine system and facility can be tolerated.
If the power is restored within the specified duration, the inverter restarts in the restart mode
specified by F14. If not, the inverter recognizes that the power has been shut down so that the
inverter does not apply the restart mode and starts normal running.
If H16 (Allowable momentary power failure time) is set to "Auto," restart will take place until
the DC link bus voltage drops down to the allowable voltage (100 V) for restart after a
momentary power failure. If the DC link bus voltage drops below the allowable voltage, the
inverter recognizes that the power has been shut down so that the inverter does not apply the
restart mode and starts normal running.
The time required from when the DC link bus voltage drops from the threshold of
undervoltage until it reaches the allowable voltage for restart after a momentary
power failure, greatly varies depending on the inverter capacity, the presence of
options, and other factors.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...