6.3 Details of Function Codes
6-119
Chap. 6
FUNCTION C
ODES
Motor 1 to Motor 8 being driven by commercial power
--
M1-L
to
M8-L
(Function code data = 161, 163, 165, 167, 169, 171, 173, and 175)
These signals are used to find motors being driven by commercial power in pump operation.
Assign these signals for motors to be driven by commercial power when the "inverter drive
motor fixed system" (J401 = 1), the "inverter drive motor floating system" (J401 = 2), or the
"inverter drive motor fl commercial power-driven motor system" (J401 = 3) is
selected.
Refer to J401.
In mutual operation --
M-RUN
(Function code data = 180)
This output signal comes ON when two or more motors are running in mutual operation (J401
= 52 or 54).
Refer to J401 through J404.
Alarm in mutual operation --
M-ALM
(Function code data = 181)
This output signal comes ON when two or more motors are stopped due to alarm in mutual
operation (J401 = 52 or 54).
Refer to J401 through J404.
Cancel timer --
TMD
(Function code data = 190)
Timer 1 to Timer 4 enabled --
TMD1
to
TMD4
(Function code data = 191 to 194)
With the combination of
TMD1
to
TMD4
, the inverter outputs the current state of timer
operation.
Refer to T01 through T19.
Output status of external output signals
Timer operation state
TMD TMD1
TMD2 TMD3 TMD4
Timer operation disabled (no setting or
being canceled)
OFF OFF OFF OFF OFF
Timer operation time invalid
OFF
OFF
OFF
OFF
OFF
Timer 1
ON
OFF OFF OFF
Timer 2
OFF
ON
OFF OFF
Timer 3
OFF
OFF
ON
OFF
Timer 4
OFF
OFF
OFF
ON
Timers 1 + 2
ON
ON
OFF OFF
Timers 1 + 3
ON
OFF
ON
OFF
Timers 1 + 4
ON
OFF OFF
ON
Timers 2 + 3
OFF
ON
ON
OFF
Timers 2 + 4
OFF
ON
OFF
ON
Timers 3 + 4
OFF
OFF
ON
ON
Timers 1 + 2 + 3
ON
ON
ON
OFF
Timers 1 + 2 + 4
ON
ON
OFF
ON
Timers 1 + 3 + 4
ON
OFF
ON
ON
Timers 2 + 3 + 4
OFF
ON
ON
ON
Timers 1 + 2 + 3 + 4
ON
ON
ON
ON
ON
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...