6.3 Details of Function Codes
6-327
Chap. 6
FUNCTION C
ODES
Notes for using a customizable logic
The customizable logic is calculated for every 5 ms and processed in the following procedure.
(1) At the start of processing, latch the external input signals to all customizable logics in
steps 1 to 14 to ensure concurrency.
(2) Execute the logic calculations from steps 1 to 14.
(3) If an output of a particular step applies to an input at the next step, the output of the step
having processing priority can be used in the same processing.
(4) The customizable logic updates 7 output signals at a time.
When configuring a logic circuit, take into account the processing order of the customizable
logic. Otherwise, a delay in processing of logical operation leads to a signal delay problem,
resulting in no expected output, slow processing, or a hazard signal issued.
Ensure safety before modifying customizable logic related function code settings (U codes and
related function codes) or turning ON the "Cancel customizable logic" terminal command
CLC
. Depending upon the settings, such modification or cancellation of the customizable logic
may change the operation sequence to cause a sudden motor start or an unexpected motor
operation.
An accident or injuries could occur.
Customizable logic timer monitor (step selection) (U91, X89 to X93)
The monitor function code can be used to monitor the input/output state in the customizable
logics and timer operation status.
Selecting a timer to be monitored
Function code
Function
Remarks
U91
0: Disable monitoring (Monitor data is set to 0.)
1 to 14: Specify the step number to be monitored.
Turning the power off
zero-clears the setting
value.
Monitoring
Monitored by:
Related function code and
LCD monitor display
Monitor item
Communications
link
X89 customizable logic (Digital
input/output)
Digital I/O data of the step
specified with U91
(monitor-specific)
X90 Customizable logic (Timer monitor) Timer/counter value specified
with U91 (monitor-specific)
X91 customizable logic (Analog input 1) Analog input 1 data of the step
specified with U91
(monitor-specific)
X92 customizable logic (Analog input 2) Analog input 2 data of the step
specified with U91
(monitor-specific)
X93 customizable logic (Analog output) Analog output data of the step
specified with U91
(monitor-specific)
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...