6-14
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
H46 Starting
Mode
(Auto search delay time 2)
0.1 to 20.0 s
Y Y1 *6
H47 Initial Capacitance of DC Link Bus
Capacitor
Meas (Measure initial value), Failed (Measurement failed),
2 to 65535
Indication for replacement of DC link bus capacitor
Y N -
H48 Cumulative Run Time of Capacitors on
Printed Circuit Boards
Indication for replacement of capacitors
0 to 99990 (in units of 10 hours)
Y N -
H49 Starting
Mode
(Auto search delay time 1)
0.0 to 10.0 s
Y Y 0.0
H50 Non-linear V/f Pattern 1
(Frequency) OFF: Cancel, 0.1 to 120.0 Hz
N Y *7
H51
(Voltage) 0 to 500: Output an AVR-controlled voltage
N Y1
E/A:
*8
C: 0
H52 Non-linear V/f Pattern 2
(Frequency) OFF: Cancel, 0.1 to 120.0 Hz
N Y
OFF
H53
(Voltage) 0 to 500: Output an AVR-controlled voltage
N Y1 0
H56 Deceleration Time for Forced Stop
0.00 to 3600 s
Y Y
20.0
H61 Multistep Fre UP/DOWN Control
(Initial frequency setting)
1: Last UP/DOWN command value on releasing the run
command
13 to 106: Multistep fre UP/DOWN command (Initial
value to be preserved)
N Y 1
H63 Low Limiter
(Mode selection) 0: Limit by F16 (Frequency limiter: Low) and continue to run
1: If the output frequency lowers below the one limited by F16
(Frequency limiter: Low), decelerate to stop the motor.
Y Y 0
H64
(Lower limiting frequency) Inherit: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
Y Y 2.0
H68 Slip Compensation 1
(Operating conditions)
0: Enable during ACC/DEC and at base frequency or above
1: Disable during ACC/DEC and enable at base frequency or
above
2: Enable during ACC/DEC and disable at base frequency or
above
3: Disable during ACC/DEC and at base frequency or above
N Y 0
H69 Automatic
Deceleration
(Mode
selection)
0: Disable
2: Torque limit control with Force-to-stop if actual deceleration
time exceeds three times the specified one
3: DC link bus voltage control with Force-to-stop if actual
deceleration time exceeds three times the specified one
4: Torque limit control with Force-to-stop disabled
5: DC link bus voltage control with Force-to-stop disabled
Y Y 0
H70 Overload Prevention Control
OFF: Cancel
Inherit: Follow the selected deceleration time
0.01 to 100.00 Hz/s
Y Y
OFF
H71 Deceleration
Characteristics
0: Disable
1: Enable
Y Y 0
H72 Main Power Down Detection
(Mode
selection)
0: Disable
1: Enable
Y Y 1
H76 Torque Limiter for Braking
(Frequency increment limit)
0.0 to 120.0 Hz
Y Y 5.0
H77 Service Life of DC Link Bus Capacitor
(Remaining
time)
0 to 43800 (in units of 10 hours)
Y N -
H78 Maintenance Interval (M1)
OFF: Disable
10 to 99990 (in units of 10 hours)
Y N
43800
H79 Preset Startup Count for Maintenance (M1) OFF: Disable
1 to 65535
Y N
OFF
H80 Output Current Fluctuation Damping Gain
for Motor 1
0.00 to 1.00
Y Y
0.20
H89 Reserved *9
0, 1
Y Y 1
H90 Reserved *9
0, 1
Y Y 0
H91 Current Input Wire Break Detection
OFF: Disable, 0.1 to 60.0 s
Y Y
OFF
H92 Continuity of Running
(P) 0.000 to 10.000 times
Auto
Y Y1
Auto
H93
(I) 0.010 to 10.000 s
Auto
Y Y1
Auto
H94 Cumulative Motor Run Time 1
0 to 99990 (The cumulative run time can be modified or reset in
units of 10 hours.)
N N -
H95 DC
Braking
(Braking response mode)
0: Slow
1: Quick
Y Y 1
H96 STOP Key Priority/Start Check Function
Data
STOP key priority
Start check function
0: Disable
Disable
1: Enable
Disable
2: Disable
Enable
3: Enable
Enable
Y Y 0
H97 Clear
Alarm
Data
0:
Disable
1: Enable (Setting "1" clears alarm data and then returns to "0.")
Y N 0
Note: Alphabets in the Default setting field denote shipping destination: E (EU), A (Asia), C (China).
*7 0.0 (Cancel) for inverters with a capacity of 22 kW or below; 5.0 Hz for those with 30 kW or above.
*8 0 V for inverters with a capacity of 22 kW or below; 40 V for inverters with 30 kW or above, respectively.
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...