6-252
Function code
Name
Data
Description
J452 Motor
decrease
judgment
(Judgment
frequency)
0 to 120 Hz, Inherit
J453 Motor
decrease
judgment
(Duration time)
0.00 to 3600 s
This function code adjusts the motor
subtracting conditions.
If the frequency of the inverter-driven pump
drops below the setting of J452 and keeps it for
the setting of J453, commercial power-driven
motor subtracting conditions are met.
The default is that if the frequency reaches the
setting of J119 (PID lower limiter), the
subtracting conditions are immediately met.
J461 Motor
increase/
decrease
switching
judgment
non-responsive
area width
OFF, 0.1 to 50.0%
If the deviation between SV and PV values is
less than the setting of J461, no increase/
decrease judgment is made.
J454 Contact
restart
time when
switching the
motor
0.01 to 2.00 s
Taking into account the contactor delay at the
time of adding motors, the start of an inverter
output can be delayed. Adjust this value when
the inverter trips due to a contactor delay.
J455 Motor
increase
switching time
(Deceleration
time)
0.00 to 3600 s, Inherit
J456 Motor
increase
switching level
0 to 100%
J457 Motor
increase
PID control
start frequency
0 to 120 Hz, Inherit
This function code adjusts the sequence to
apply at the time of adding motors. If the
adding conditions of commercial power-driven
pumps are met, the inverter decelerates
according to the setting of J455. If the inverter
decelerates to the setting of J456, it turns the
commercial power-driven pump start signal
ON. After that, the inverter continues to
decelerate. When it reaches the setting of J457,
it restarts PID control.
J456 is a percentage within the PID control
range (lower to upper limits).
The initial speed decelerates according to the
deceleration time selected. When it drops to
the PID lower limit frequency, the start signal
comes ON.
J458 Motor
decrease
switching time
(Acceleration
time)
0.00 to 3600 s, Inherit
J459 Motor
decrease
switching level
0 to 100%
J460 Motor
decrease
PID control
start frequency
0 to 120 Hz, Inherit
This function code adjusts the sequence to
apply at the time of motor decrease. If the
subtracting conditions of commercial
power-driven pumps are met, the inverter
accelerates according to the setting of J458. If
the inverter accelerates to the setting of J459, it
turns the commercial power-driven pump start
signal ON. After that, the inverter continues to
accelerate. When it reaches the setting of J460,
it restarts PID control.
J459 is a percentage within the PID control
range (lower to upper limits).
The initial speed accelerates according to the
acceleration time selected. When it rises to the
PID upper limit frequency, the start signal
comes ON.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...