8-6
8.1.4
Communications support devices
This section describes the devices required for connecting the inverter to a PC having no RS-485
interface or for connecting two or more inverters in multi-drop network.
[ 1 ] Communications level converters
Usually PCs are not equipped with an RS-485 communications port but with an RS-232C port. To
connect inverters to a PC, therefore, you need an RS-232C–RS-485 converter or a USB–RS-485
converter. To run the FRENIC-AQUA correctly, use a converter satisfying the requirements given
below.
Requirements for recommended communications level converters
Send/receive switching:
Auto-switching by monitoring of send/receive data status at the PC
(RS-232C)
Electric isolation:
Electrically isolated from the RS-485 port
Fail-safe:
Fail-safe facility*
Other requirements:
Superior noise immunity
*
The fail-safe facility refers to a feature that ensures the RS-485 receiver's output at "High" (logical
value = 0) even if the RS-485 receiver's input is opened or short-circuited or all the RS-485 drivers
are inactive. Refer to Figure 8.3.
Recommended converters
System Sacom Sales Corporation (Japan) : KS-485PTI (RS-232C
−
RS-485 converter)
: USB-485I RJ45-T4P (USB
−
RS-485 converter)
Send/receive switching system
The RS-485 communications system of the inverter acts in half-duplex mode (2-wire) so the converter
must feature a send/receive switching circuitry. Generally, the switching system may be either one of
the following.
(1) Auto-switching by monitoring of send/receive data
(2) Switching by RS-232C control signal of RTS or DTR (hardware flow control system)
Figure 8.3 Communications Level Conversion
FRENIC-AQUA (two-wire system)
RS-232C
—
RS-485 converter
RS-485
Computer
送受信切換
Level
conversi
on
Driver
Receiver
Transmission/
receiving
switching
Driver input
Receiver enable
Receiver
Receiver output
Driver input
Driver
Driver enable
Receiver enable
Driver
enable
Receiver output
RS-232C
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...