E01 Terminal [X1] Function
N Y 0
E02 Terminal [X2] Function
N Y 1
E03 Terminal [X3] Function
N Y 6
E04 Terminal [X4] Function
N Y 7
E05 Terminal [X5] Function
N Y 8
E06 Terminal [X6] Function
N Y 11
E07 Terminal [X7] Function
Selecting function code data assigns the corresponding function
to terminals [X1] to [X7] as listed below.
0 (1000):
Select multistep frequency (0 to 1 steps)
(
SS1
)
1 (1001):
Select multistep frequency (0 to 3 steps)
(
SS2
)
2 (1002):
Select multistep frequency (0 to 7 steps)
(
SS4
)
3 (1003):
Select multistep frequency (0 to 15 steps)
(
SS8
)
4 (1004):
Select ACC/DEC time (2 steps)
(
RT1
)
5 (1005):
Select ACC/DEC time (4 steps)
(
RT2
)
6 (1006):
Enable 3-wire operation
(
HLD
)
7 (1007):
Coast to a stop
(
BX
)
8 (1008):
Reset alarm
(
RST
)
9 (1009):
Enable external alarm trip
(
THR
)
(9 = Active OFF, 1009 = Active ON)
11 (1011): Select frequency command 2/1
(
Hz2/Hz1
)
13:
Enable DC braking
(
DCBRK
)
14 (1014): Select torque limiter level 2/1
(
TL2/TL1
)
15:
Switch to commercial power (50 Hz)
(
SW50
)
16:
Switch to commercial power (60 Hz)
(
SW60
)
17 (1017): UP (Increase output frequency)
(UP)
18 (1018): DOWN (Decrease output frequency)
(DOWN)
19 (1019): Enable data change with keypad
(WE-KP)
20 (1020): Cancel PID control
(Hz/PID)
21 (1021): Switch normal/inverse operation
(
IVS
)
22 (1022): Interlock
(
IL
)
24 (1024): Enable communications link via
RS-485 or fieldbus (option)
(
LE
)
25 (1025): Universal DI
(
U-DI
)
26 (1026): Enable auto search for idling motor
speed at starting
(
STM
)
30 (1030): Force to stop
(
STOP
)
(30 = Active OFF, 1030 = Active ON)
33 (1033): Reset PID integral and differential
components (
PID-RST
)
34 (1034): Hold PID integral component
(
PID-HLD
)
35 (1035): Select local (keypad) operation
(
LOC
)
38 (1038): Enable run commands
(
RE
)
39:
Protect motor from dew condensation
(
DWP
)
40:
Enable integrated sequence to switch
to commercial power (50 Hz)
(
ISW50
)
41:
Enable integrated sequence to switch
to commercial power (60 Hz)
(
ISW60
)
50 (1050): Clear running motor regular switching time (
MCLR
)
58 (1058): Reset UP/DOWN frequency
(
STZ
)
72 (1072): Count the run time of commercial
power-driven motor 1
(
CRUN-M1
)
80 (1080): Cancel customizable logic
(
CLC
)
81 (1081): Clear all customizable logic timers
(
CLTC
)
87 (1087): Run command 2/1
(
FR2/FR1
)
88: Run
forward
2
(
FWD2
)
89: Run
reverse
2
(
REV2
)
100:
No function assigned
(
NONE
)
130 (1130): Boost command
(
BST
)
131 (1131): Flowrate switch
(
FS
)
132 (1132): Filter clogging reverse rotation command
(
FRC
)
133 (1133): Switch PID channel
(
PID2/1
)
134:
Switch to fire mode
(
FMS
)
149 (1149): Switch pump control
(
PCHG
)
150 (1150): Enable master motor drive in mutual
operation (
MENO
)
151 (1151): Enable pump control motor 1 to be driven (
MEN1
)
152 (1152): Enable pump control motor 2 to be driven (
MEN2
)
153 (1153): Enable pump control motor 3 to be driven (
MEN3
)
154 (1154): Enable pump control motor 4 to be driven (
MEN4
)
155 (1155): Enable pump control motor 5 to be driven (
MEN5
)
156 (1156): Enable pump control motor 6 to be driven (
MEN6
)
157 (1157): Enable pump control motor 7 to be driven (
MEN7
)
158 (1158): Enable pump control motor 8 to be driven (
MEN8
)
171 (1171): PID multistep command 1
(
PID-SS1
)
172 (1172): PID multistep command 2
(
PID-SS2
)
181 (1181): External PID multistep command
(
EPID-SS1
)
182 (1182): External PID multistep command
(
EPID-SS2
)
N Y 35
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...