6.3 Details of Function Codes
6-173
Chap. 6
FUNCTION C
ODES
•
Ensure that transistor output signals ([Y1] to [Y4]) and relay output signals ([Y5A] -
[Y5C], and [30A/B/C]) will not be turned ON.
•
Disable the RS-485 communications link.
If negative logic is specified for the transistor output and relay output signals,
they are considered ON when the inverter is not running. Specify positive
logic for them.
•
Keep the ambient temperature within 25
±
10
°
C.
2) Turn ON the main circuit power.
3) Confirm that the inverter is in a stopped state.
4) Turn OFF the main circuit power.
5) The inverter automatically starts the measurement of the capacitance of the DC link bus
capacitor. Check that "Capacitor capacitance measurement" is shown on the LCD
monitor.
In a case where "Capacitor capacitance measurement" is not shown on the LCD
monitor, measurement is not yet started.
6) After " . . . . " has disappeared from the LCD monitor, turn ON the main circuit power
again.
7) Select PRG > 3(INV Info) > 4(Maintenance) in Programming mode and note the reading
(relative capacitance (%) of the DC link bus capacitor).
---------------------------------------------------------------------------------------------------------------
[ 2 ] Measuring the capacitance of DC link bus capacitor under ordinary
operating conditions
When bit 3 of H98 data is 1, the inverter automatically measures the capacitance of the DC
link bus capacitor under ordinary operating conditions when the power is turned OFF. This
measurement requires setting up the load conditions for ordinary operation and measuring the
reference capacitance when the inverter is introduced to the practical operation, using the
setup procedure given below.
Function
code
Name Data
H42
Capacitance of
DC link bus
capacitor
• Capacitance of DC link bus capacitor (measured value)
• Start of initial capacitance measuring mode under ordinary
operating conditions (Meas)
• Measurement failure (Failed)
H47
Initial
capacitance of
DC link bus
capacitor
• Initial capacitance of DC link bus capacitor (measured value)
• Start of initial capacitance measuring mode under ordinary
operating conditions (Meas)
• Measurement failure (Failed)
When replacing parts, clear or modify the H42 and H47 data. For details, refer to the
documents for maintenance.
---------------------------- Reference capacitance setup procedure ----------------------------
1) Set function code H98 (Protection/maintenance function) to enable the user to specify the
judgment criteria for the service life of the DC link bus capacitor (Bit 3 = 1) (refer to
function code H98).
2) Turn OFF all run commands.
3) Make the inverter ready to be turned OFF under ordinary operating conditions.
4) Set both function codes H42 (Capacitance of DC link bus capacitor) and H47 (Initial
capacitance of DC link bus capacitor) to "Meas." (Setting H47 to "Meas" automatically
sets H42 to "Meas.")
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...