6-62
Restart mode after momentary power failure (Basic operation: Auto search disabled)
The inverter recognizes a momentary power failure upon detecting the condition that DC link
bus voltage goes below the undervoltage level, while the inverter is running. If the load of the
motor is light and the duration of the momentary power failure is extremely short, the voltage
drop may not be great enough for a momentary power failure to be recognized, and the motor
may continue to run uninterrupted.
Upon recognizing a momentary power failure, the inverter enters the restart mode (after a
recovery from momentary power failure) and prepares for restart. When power is restored,
the inverter goes through an initial charging stage and enters the ready-to-run state. When a
momentary power failure occurs, the power supply voltage for external circuits such as relay
sequence circuits may also drop so as to turn the run command OFF. In consideration of such
a situation, the inverter waits 2 seconds for a run command input after the inverter enters a
ready-to-run state. If a run command is received within 2 seconds, the inverter begins the
restart processing in accordance with the F14 data (Mode selection). If no run command has
been received within 2-second wait period, the inverter cancels the restart mode (after a
recovery from momentary power failure) and needs to be started again from the ordinary
starting frequency. Therefore, ensure that a run command is entered within 2 seconds after
recovery of power or held with an off-delay timer or a mechanical latch relay.
When run commands are entered via the keypad, the above operation is also necessary for the
mode (F02 = 0) in which the rotational direction is determined by the terminal command,
FWD
or
REV
. In the modes where the rotational direction is fixed (F02 = 2 or 3), the run
command is retained inside the inverter so that the restart will begin as soon as the inverter
enters the ready-to-run state.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...