6-100
Selection of Commercial Power Switching Sequence
J22 specifies whether or not to automatically switch to commercial-power operation when an
inverter alarm occurs.
Data for J22
Sequence (upon occurrence of an alarm)
0
Keep inverter-operation (Stop due to alarm.)
1
Automatically switch to commercial-power operation
• The sequence operates normally also even when
SW52-1
is not used and the
main power of the inverter is supplied at all times.
• Using
SW52-1
requires connecting the input terminals [R0] and [T0] for an
auxiliary control power. Without the connection, turning
SW52-1
OFF loses also
the control power.
• The sequence operates normally even if an alarm occurs in the inverter except
when the inverter itself is broken. Therefore, for a critical facility, be sure to
install an emergency switching circuit outside the inverter.
• Turning ON both the magnetic contactor MC (88) at the commercial-power side
and the MC (52-2) at the inverter output side at the same time supplies main
power mistakenly from the output (secondary) side of the inverter, which may
damage the inverter. To prevent it, be sure to set up an interlocking logic outside
the inverter.
Examples of Sequence Circuits
1) Standard
sequence
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...