6.3 Details of Function Codes
6-117
Chap. 6
FUNCTION C
ODES
Motor overheat detected by thermistor --
THM
(Function code data = 56)
Even when the PTC thermistor on the motor detects an overheat, the inverter turns this signal
ON and continues to run, without entering the alarm
OH4
state. This feature applies only
when H26 data is set to "2."
Refer to H26 and H27.
Terminal [C1] wire break --
C1OFF
(Function code data = 59)
This output signal comes ON when the inverter detects that the input current to terminal [C1]
drops below 2 mA interpreting it as the terminal [C1] wire broken.
Motor regular switching early warning --
MCHG
(Function code data = 68)
This outputs a motor regular switching early warning signal.
Refer to J437.
Pump control output limit signal --
MLIM
(Function code data = 69)
When the pump control mode selection is enabled (J401
≠
0), all of the enabled motors are to
be driven. With all motors being driven, if the motor increase judgment is established by the
motor increase judgment (Judgment frequency) (J450) and (Duration time) (J451), the
inverter issues an
MLIM
signal.
This signal detects the discharge rate (pressure) remaining low due to pump pipe rupture. etc.
Maintenance timer --
MNT
(Function code data = 84)
Once the inverter's cumulative run time or the startup times for the motor 1 exceeds the
previously specified count, this output signal comes ON.
Refer to H44, H78 and H79.
Frequency arrival signal (with frequency detection)
--
FARFDT
(Function code data = 87)
This output signal comes ON when both the
FAR
(Frequency arrival signal) and
FDT
(Frequency detected) come ON. (The
FARFDT
is an AND condition signal of the
FAR
and
FDT
.)
Auxiliary motor drive signal --
AUX_L
(Function code data = 88)
This output signal comes ON when all motors enabled by
MEN1
to
MEN8
(Enable pump
control motor 1 to 8 to be driven) are running and the frequency of inverter-driven motors
reaches the frequency operation level of the auxiliary motor (J465).
When the frequency of inverter-driven motors drops below the hysteresis width of the
auxiliary motor (J466), this signal goes OFF.
When PID control is disabled (J101/J201 = 0) or pump control is disabled (J401 = 0), this
output signal is OFF.
Refer to J465 to J469.
Running in fire mode --
FMRUN
(Function code data = 95)
This output signal comes ON in fire mode.
Refer to H116 through H121.
Light alarm --
L-ALM
(Function code data = 98)
This output signal comes ON when a light alarm occurs.
Refer to H181 through H184.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...