6-180
H63
Low Limiter (Mode selection)
(
Refer to F15.)
For details, refer to the description of F15.
H64
Low Limiter (Lower limiting frequency)
H64 specifies the lower limit of frequency to be applied when the current limiter, torque
limiter, automatic deceleration (anti-regenerative control), or overload prevention control is
activated. Normally, it is not necessary to change this data.
- Data setting range: 0.0 to 60.0 (Hz)
H68
Slip Compensation 1 (Operating conditions)
(
Refer to F42.)
For details, refer to the description of F42.
H69
Automatic Deceleration (Mode selection)
H76 (Torque Limiter for Braking, Frequency increment limit)
H69 toggles anti-regenerative control on and off.
In the inverter not equipped with a PWM converter or braking unit, if the regenerative energy
returned exceeds the inverter's braking capability, an overvoltage trip occurs.
To avoid such an overvoltage trip, enable the automatic deceleration (anti-regenerative
control) with this function code, and the inverter controls the output frequency to keep the
braking torque around 0 N·m in both the acceleration/deceleration and constant speed
running phases.
The FRENIC-AQUA series of inverters have two braking control modes; torque limit control
and DC link bus voltage control. Understand the feature of each control and select the suitable
one.
Control mode
Control process
Operation mode
Features
Torque limit
control
(H69=2 or 4)
Output frequency is
controlled so that the
braking torque is kept
at the regeneration
avoidance operation
level (H114).
Enabled during
acceleration, running
at the constant speed,
and deceleration.
Quick response.
Causes less
overvoltage trip with
heavy impact load.
DC link bus
voltage control
(H69=3 or 5)
Control the output
frequency to lower
the DC link bus
voltage if the voltage
exceeds the limiting
level.
Enabled during
deceleration.
Disabled during
running at the
constant speed.
Shorter deceleration
time by making good
use of the inverter's
regenerative
capability.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...