6-4
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
F31 Analog Output [FM1]
(Function) Select a function to be monitored from the followings.
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Output
current
3: Output
voltage
4: Output
torque
5: Load
factor
6: Input
power
7: PID
feedback
amount
9: DC link bus voltage
10: Universal
AO
13: Motor output
14: Calibration (+)
15: PID command (SV)
16: PID output (MV)
18: Inverter heat sink temperature (200°C/10 V)
20: Reference frequency
50: PID feedback amount 1 (PV1)
51: PID command 1 (SV1)
52: PID deviation 1 (ERR1) (Note 1)
53: PID final deviation (ERR) (Note 1)
54: PID feedback amount 2 (PV2)
55: PID command 2 (SV2)
56: PID deviation 2 (ERR2) (Note 1)
60: External PID feedback amount 1 (EPID1-PV)
61: External PID command 1 (EPID1-SV)
62: External PID deviation 1 (EPID1-ERR) (Note 1)
63: External PID final deviation 1 (EPID-ERR) (Note 1)
65: External PID final output 1 (EPID1-OUT)
70: External PID feedback amount 2 (EPID2-PV)
71: External PID command 2 (EPID2-SV)
72: External PID deviation 2 (EPID2-ERR) (Note 1)
75: External PID final output 2 (EPID2-OUT)
80: External PID feedback amount 3 (EPID3-PV)
81: External PID command 3 (EPID3-SV)
82: External PID deviation 3 (EPID3-ERR) (Note 1)
85: External PID final output 3 (EPID3-OUT)
111: Customizable logic output signal 1
112: Customizable logic output signal 2
113: Customizable logic output signal 3
114: Customizable logic output signal 4
115: Customizable logic output signal 5
116: Customizable logic output signal 6
117: Customizable logic output signal 7
(Note 1) Deviation output is supported only by option terminal
[Ao] (o09).
Y Y 0
F32 Pulse Output [FM2]
(Mode selection) 0: Voltage (0 to +10 VDC)
1: Current (4 to +20 mA DC)
2: Current (0 to +20 mA DC)
Y Y 0
F34
(Voltage adjustment) 0 to 300%
Y* Y 0
F35
(Function) Same as F31.
Y Y 0
F37 Load
Selection/
Auto Torque Boost/
Auto Energy Saving Operation 1
0: Variable
torque
load
1: Constant
torque
load
2: Auto
torque
boost
3: Auto energy saving
(Variable torque load during ACC/DEC)
4: Auto energy saving
(Constant torque load during ACC/DEC)
5: Auto energy saving
(Auto torque boost during ACC/DEC)
N Y 1
F40 Torque
Limiter
1
(Driving)
F41
(Braking)
OFF: Disable
20% to 150%: Torque limiter level
Y Y
OFF
F42 Drive Control Selection 1
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
N Y 0
F43 Current Limiter
(Mode selection) 0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
Y Y 2
F44
(Level) 20% to 120% (Assuming the inverter rated current as 100%.)
Y Y 120
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......