Description
The ground bar kit fits the following drives in E1h and E2h
enclosures:
•
VLT
®
HVAC Drive FC 102
•
VLT
®
Refrigeration Drive FC 103
•
VLT
®
AQUA Drive FC 202
•
VLT
®
AutomationDrive FC 302
The kit includes a pair of ground bars for installation inside
E1h/E2h enclosures.
Kit Part Numbers
Use these instructions with the following kits.
Kit number
Kit description
176F6609
Ground bar kit for E1h/E2h drives
Table 1.1 Part Numbers for Kits
Items Supplied
The ground bar kit contains the following items.
Item
Quantity
Ground bar
2
Angle bracket
2
M5x18 mm screw
4
M6 hex nut
4
Table 1.2 Items Supplied in Ground Bar Kit
Safety Information
WARNING
ELECTRICAL SHOCK HAZARD
VLT
®
FC series drives contain dangerous voltages when
connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
•
Only use qualified electricians for the installation.
•
Disconnect the drive from all power sources before
installation or service.
•
Treat the drive as live whenever the mains voltage
is connected.
•
Follow the guidelines in these instructions and local
electrical safety codes.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High voltage
can be present even when the warning LED indicator lights
are off. Failure to wait 40 minutes after power has been
removed before performing service or repair work can result
in death or serious injury.
•
Stop the motor.
•
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.
•
Disconnect or lock PM motor.
•
Wait 40 minutes for capacitors to discharge fully.
•
Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.
Installation Instructions
Ground Bar Kit for E1h/E2h Drives
VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
Danfoss A/S © 10/2017 All rights reserved.
MI35K102