6-224
Slow flowrate stop function (Operation level) (J150, J250)
Select an operation level to be used as the slow flowrate stop condition. Set PID control 1 and
PID control 2 with function codes J150 and J250 respectively.
- Data setting range: See the table below.
Data for J149
and J249
Setting range for
J150 and J250
Remarks
1, 11, 21
Automatically calculates the best value from the
maximum frequency (F03)
2, 12, 22
Auto
Automatically calculates the best value from SV
1, 11, 21
0.0 to 120.0 Hz
Setting with a frequency
2, 12, 22
0.00 to 9990.00
Setting with physical quantity
PID control 1: display unit (J105), scale (J106, J107)
PID control 2: display unit (J205), scale (J206, J207)
(Setting range is limited by maximum scale and
minimum scale.)
Slow flowrate stop function (Elapsed time) (J151, J251)
Set time delay from PID output's satisfaction of the stop conditions specified with Mode
selection (J149, J249) and operation level (J150, J250) until the inverter starts to decelerate
and stop. Set PID control 1 and PID control 2 with function codes J151 and J251 respectively.
- Data setting range: 0 to 60 (s)
Slow flowrate stop function (Auto-operation frequency lower-limit) (J152)
J152 specifies the lower limit of the stop judgment level (output frequency) to be recorded by
shutoff operation when J149 = 11 or 21.
- Data setting range: 0.0 to 120.0 (Hz)
Slow flowrate stop function (Pressurization starting frequency) (J153)
- Data setting range: 0.0 to 120.0 (Hz)
Slow flowrate stop function (Pressurizing time) (J154)
- Data setting range: 0 to 60 (s)
Specifying J153 (Pressurization starting frequency) and J154 (Pressurizing time) enables
pressurization control when the frequency drops below the level specified by J149 (Stop
frequency for slow flowrate) for the period specified by J151. During the pressurization, PID
control is in the hold state.
This function prolongs the stopping time of equipment with a bladder tank by pressurizing
immediately before the frequency drops below the level at which the inverter stops the motor,
thus enabling energy saving operation.
Because the pressurization starting frequency (J153) can be specified with a parameter,
pressurization setting suitable for the equipment is possible.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...