9.3 If an Alarm Code Appears on the Monitor
9-13
Chap. 9
TROUBL
ESH
OOTING
[ 21 ] Er7 Tuning error
Problem Auto-tuning
failed.
Possible Causes
What to Check and Suggested Measures
(1) A phase was missing (There was a
phase loss) in the connection
between the inverter and the
motor.
Î
Properly connect the motor to the inverter.
(2) V/f or the rated current of the
motor was not properly set.
Check whether the data of function codes (F04, F05, H50 through
H53, P02, and P03) matches the motor specifications.
(3) The wiring length between the
inverter and the motor was too
long.
Check whether the wiring length between the inverter and the motor
exceeds 50 m.
(Inverters with a small capacity are greatly affected by the wiring
length.)
Î
Review, and if necessary, change the layout of the inverter and the
motor to shorten the connection wire. Alternatively, minimize the
wiring length without changing the layout.
Î
Disable both auto-tuning and auto-torque boost (set data of F37 to
"1").
(4) The rated capacity of the motor
was significantly different from
that of the inverter.
Check whether the rated capacity of the motor is three or more ranks
lower, or two or more ranks higher than that of the inverter.
Î
Replace the inverter with one with an appropriate capacity.
Î
Manually specify the values for the motor parameters P06, P07,
and P08.
Î
Disable both auto-tuning and auto-torque boost (set data of F37 to
"1").
(5) The motor was a special type such
as a high-speed motor.
Î
Disable both auto-tuning and auto-torque boost (set data of F37 to
"1").
(6) A tuning operation involving
motor rotation (P04 = 2 or 3) was
attempted while the brake was
applied to the motor.
Î
Specify the tuning that does not involve the motor rotation (P04 =
1).
Î
Release the brake before tuning that involves the motor rotation
(P04 = 2 or 3).
For details of tuning errors, refer to the FRENIC-AQUA Instruction Manual, Chapter 5, Section 5.7.9
"Function code basic settings and tuning < 2 >,
Tuning errors."
Preparation before running the motor for a test – Setting function code data."
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...