6.3 Details of Function Codes
6-95
Chap. 6
FUNCTION C
ODES
• When process control is performed by the PID processor integrated in the inverter:
The terminal command
Hz
/
PID
("Cancel PID control") can switch PID control between
enabled (process is to be controlled by the PID processor) and disabled (process is to be
controlled by the manual frequency setting). In either case, the combination of the "PID
control" (J101, J201) or "Selection of normal/inverse operation for frequency command 1"
(C53) and the terminal command
IVS
determines the final operation as listed below.
When PID control is enabled:
The normal/inverse operation selection for the PID processor output (reference frequency) is
as follows.
PID control (Mode selection)
(J101, J201)
IVS
Final operation
OFF
Normal
1: Enable (normal operation)
ON
Inverse
OFF
Inverse
2: Enable (inverse operation)
ON
Normal
When PID control is disabled:
The normal/inverse operation selection for the manual reference frequency is as follows.
Selection of normal/inverse operation
for frequency command 1 (C53)
IVS
Final operation
0: Normal operation
–
Normal
1: Inverse operation
–
Inverse
When process control is performed by the PID control facility integrated in the
inverter, the
IVS
is used to switch the PID processor output (reference frequency)
between normal and inverse, and has no effect on any normal/inverse operation
selection of the manual frequency setting.
Refer to the descriptions of J101 through J138 and J201 through J231.
Interlock --
IL
(Function code data = 22)
In a configuration where a magnetic contactor (MC) is installed in the power output
(secondary) circuit of the inverter, the momentary power failure detection feature provided
inside the inverter may not be able to accurately detect a momentary power failure by itself.
Using a digital signal input with the interlock command
IL
assures the accurate detection.
Refer to F14.
Terminal command
IL
Meaning
OFF
No momentary power failure has occurred.
ON
A momentary power failure has occurred.
(Restart after a momentary power failure enabled)
Enable communications link via RS-485 or fieldbus (option)
--
LE
(Function code data = 24)
Turning this terminal command ON gives priorities to frequency commands or run
commands received via the RS-485 communications link (H30) or the fieldbus option (y98).
No
LE
assignment is functionally equivalent to the
LE
being ON.
Refer to H30 (Communications link function) and y98 (Bus link function).
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...