6-334
6.3.16 y codes (Link functions)
y01 to y20
RS-485 Communication 1 and 2
Up to two RS-485 communications ports are available as listed below.
Port
Route
Function code
Applicable equipment
Port 1 RS-485 communications link
(via the RJ-45 connector prepared for
keypad connection)
y01 through y10
Standard keypad
FRENIC Loader
Host equipment
Port 2 RS-485 communications link
(via terminals DX+, DX- and SD on the
control PCB)
y11 through y20
Inverter support loader
(FRENIC loader)
To connect any of the applicable devices, follow the procedures shown below.
(1) Standard keypad
The standard keypad allows you to run and monitor the inverter.
It can be used independent of the y code setting.
(2) FRENIC Loader
Connecting your computer running FRENIC Loader to the inverter via the RS-485
communications link (port 1 and 2), you can monitor the inverter’s running status information,
edit function codes, and test-run the inverters.
For the setting of y codes, refer to the descriptions of y01 to y20.
FRENIC-AQUA series of inverters has a USB port.
To use the FRENIC Loader via the USB port, simply set the station address (y01 or
y20) to "1" (factory default).
(3) Host equipment
The inverter can be managed and monitored by connecting host equipment such as a PC and
PLC to the inverter. Modbus RTU, Metasys N2, BACnet and Fuji general-purpose inverter
protocol are available for communications protocols.
For details, refer to the RS-485 Communication User's Manual.
Station address (y01 for port 1 and y11 for port 2)
y01 or y11 specifies the station address for the RS-485 communications link. The table below
lists the protocols and the station address setting ranges.
Protocol
Station address
Broadcast address
Modbus RTU protocol
1 to 247
0
SX protocol (FRENIC Loader
command protocol)
1 to 255
-
FRENIC Loader protocol
1 to 255
None
FUJI general-purpose inverter protocol
1 to 31
99
Metasys N2
0 to 255
-
BACnet
0 to 127
255
- If any wrong address beyond the above range is specified, no response is returned since the
inverter will be unable to receive any enquiries except the broadcast message.
- To use FRENIC Loader via the RS-485 communications link (port 1 and 2), set the station
address that matches the connected computer.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...