4.3 Peripheral Equipment
4-7
Chap. 4
SEL
ECT
ING PE
RIPH
ER
AL
EQUI
PME
N
T
Table 4.4 Rated Current of Molded Case Circuit Breaker (MCCB), Residual-Current-Operated Protective
Device (RCD)/Earth Leakage Circuit Breaker (ELCB) and Magnetic Contactor (MC)
MC
Power supply
voltage
Nominal
applied motor
(kW)
Inverter type
MCCB,
RCD/ELCB
Rated current (A) For input circuit For output circuit
0.75 FRN0.75AQ1
-4
1.5 FRN1.5AQ1
-4
5
2.2 FRN2.2AQ1
-4
3.7
(4.0)
*1
FRN3.7AQ1
-4
FRN4.0AQ1
■
-4E
10
5.5 FRN5.5AQ1
-4
15
SC-05
7.5 FRN7.5AQ1
-4
20
SC-05
11 FRN11AQ1
-4
30
SC-05
SC-4-0
15 FRN15AQ1
-4
40 SC-5-1
SC-5-1
18.5 FRN18.5AQ1
-4
22 FRN22AQ1
-4
50 SC-N1
SC-N1
30 FRN30AQ1
-4
75 SC-N2
SC-N2
37 FRN37AQ1
-4
100 SC-N2S
SC-N2S
45 FRN45AQ1
-4
100
SC-N3
55 FRN55AQ1
-4
125
SC-N3
SC-N4
75 FRN75AQ1
-4
175 SC-N4
SC-N5
90 FRN90AQ1
-4
200 SC-N7
SC-N7
110 FRN110AQ1S-4
250
132 FRN132AQ1S-4
300
SC-N8 SC-N8
160 FRN160AQ1S-4
350 SC-N11
SC-N11
200 FRN200AQ1S-4
220 FRN220AQ1S-4
500 SC-N12
SC-N12
280 FRN280AQ1S-4
600
315 FRN315AQ1S-4
355 FRN355AQ1S-4
800
SC-N14 SC-N14
400 FRN400AQ1S-4
SC-N16
SC-N16
500 FRN500AQ1S-4
1200
610CM
*2
610CM
*2
630 FRN630AQ1S-4
1400
612CM
*2
612CM
*2
Three-phase
400 V
710 FRN710AQ1S-4
1600
616CM
*2
616CM
*2
*1 4.0 kW for the EU. The inverter type is FRN4.0AQ1
-4E.
*2 The 610CM, 612CM, and 616CM are manufactured by Aichi Electric Works Co., Ltd.
Note:
A box (
) replaces an alphabetic letter depending on the enclosure.
M (IP21) or L (IP55)
A box (
) replaces an alphabetic letter depending on the shipping destination.
E (EU), A (Asia), or C (China)
- Install the MCCB or RCD/ELCB at the input side of the inverter. They cannot be installed at the
output side of the inverter.
- The above table lists the rated current of MCCBs and RCDs/ELCBs to be used in the power control
panel with an internal temperature of lower than 50
°
C. The rated current is factored by a correction
coefficient of 0.85 as the MCCBs' and RCD's/ELCBs' original rated current is specified when using
them in an ambient temperature of 50
°
C or lower. Select an MCCB and/or RCD/ELCB suitable for
the actual short-circuit breaking capacity needed for your power systems.
- For the selection of the MC type, it is assumed that the
600 V HIV wires (allowable ambient
temperature: 75
°
C)
for the power input/output of the inverter are used. If an MC type for another
class of wires is selected, the wire size suitable for the terminal size of both the inverter and the MC
type should be taken into account.
- Use RCDs/ELCBs with overcurrent protection.
- To protect your power systems from secondary accidents caused by the broken inverter, use an
MCCB and/or RCD/ELCB with the rated current listed in the above table. Do not use an MCCB or
RCD/ELCB with a rating higher than that listed.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...